Operation
Gauge driver outputs
The gauge outputs operate when CANdrive reads valid J1939
data for engine speed, oil pressure and coolant temperature.
If CANdrive stops receiving valid data, the gauge outputs
are maintained at the last known value for approximately
5 seconds, after which time the outputs turn off.
Indicating LEDs
All standard models have a green CAN LED. A flashing
CAN LED indicates that CANdrive is powered, but is not
receiving any J1939 data. A constantly lit CAN LED indicates
power on with good CANbus connection and J1939 activity.
(Note: J1939 activity can originate from ANY device on the
CANbus network, and may not necessarily be valid data from
the engine ECU.)
Model CDV300R has additional LEDs for indication of J1939-
transmitted engine faults. CANdrive responds to single
DM1 (active fault code) messages that contain SPN (Suspect
Parameter Number), FMI (Fault Mode Indicator) and
warning/stop lamp data. CANdrive also reads multi-packet
transport messages broadcast using the BAM protocol.
Typically, LEDs light continuously to indicate a shutdown fault,
and flash to indicate a (non-shutdown) warning fault:
LED Mode Fault
J1939
SPN FMI
On
Low oil pressure shutdown
100
1
Flashing Low oil pressure warning
100 > 1
On Coolant
temperature
shutdown
110
0
Flashing Coolant temperature warning 110 > 0
On Overspeed
shutdown
190
0
Flashing Overspeed warning
190 > 0
-
Reserved for future use
- -
-
Reserved for future use
- -
Flashing Warning
fault
- -
Flashing Shutdown
fault
- -
CANdrive can handle up to 8 simultaneous faults at
one time: additional fault messages are not registered.
When a fault becomes inactive and is no longer broadcast,
the appropriate LED goes out after approximately 2 seconds.
Maintenance and Warranty
CANdrive has no user-serviceable parts. Maintenance is
therefore limited to the following preventative checks:
x
Check that electrical connections are secure.
x
Check that the CANdrive is securely mounted, and
kept free from ingress of water or build up of excessive
dust/dirt. The front label and casing may be wiped with
a clean, damp cloth. Do not use cleaning solvents.
CANdrive is supplied with a 2 year warranty on parts and
workmanship. In the event of a fault or technical query, please
contact your Murphy representative for technical support.
Further information
Document Description
00-02-0251 EG(S)21 series electric gage installation
00-02-0258 AT series tachometer installation
Operation and Maintenance
FW MURPHY
P.O. Box 470248, Tulsa, Oklahoma 74147 USA
+1 918 317 4100 Fax: +1 918 317 4266
E-mail: [email protected]
INDUSTRIAL PANEL DIVISION
Fax: +1 918 317 4124
E-mail: [email protected]
MURPHY POWER IGNITION
Website: www.murphy-pi.com
CONTROL SYSTEMS AND SERVICES DIVISION
P.O. Box 1819, Rosenberg, Texas 77471 USA
Phone: +1 281 633 4500 Fax: +1 281 633 4588
E-mail: [email protected]
FRANK W. MURPHY LTD.
Church Road, Laverstock,
Salisbury, SP1 1QZ, United Kingdom
Tel: +44 1722 410055
Fax: +44 1722 410088
E-mail: [email protected]
Web: www.fwmurphy.co.uk
COMPUTRONIC CONTROLS
41 – 46 Railway Terrace, Nechells,
Birmingham, B7 5NG, United Kingdom
E-mail: [email protected]
Web: www.computroniccontrols.com
FW MURPHY INSTRUMENTS (HANGZHOU) CO., LTD.
77 23
rd
Street, Hangzhou Economic & Technological Development Area
Hangzhou, Zhejiang, 310018, China
Phone: +86 571 8788 6060 Fax: +86 571 8684 8878
E-mail: [email protected]