background image

www.murata-ps.com/support

DMS-20PC-4/20 Series

Subminiature 4-20mA Loop-Powered 

3½ Digit LED Process Monitors

MPM_DMS20PC-4/20.D01 

Page 4 of 6

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

1.

  Desired display readings are: 

  

 

4mA 

“650”

  

20mA  =  “950”

 

Use DIP-switch setting #4 in Table 3 since subtracting 650 from 950 
yields a differential value of 300. Apply 4mA and adjust R3 until the 
display reads “000”. Apply 20mA and adjust R7 until the display reads 
“300” (the differential value previously calculated). Apply 4mA and 
adjust R3 until the display reads “650”. Apply 20mA and verify that the 
display reads “950”. 

2.

  Desired display readings are:

  

 

4mA 

“4.00”

  

20mA  =  “19.99”

 

This example illustrates the DMS-20PC-4/20P’s capability to display 
higher differential readings than those indicated in Table 3. This 
example also illustrates how the DMS-20PC-4/20P can be used to 
display the output levels of a 4-20mA loop transmitter with higher preci-
sion (0.01mA versus 0.1mA) than described above. 

 

Subtracting 400 from 1999 yields a differential of 1599, a value not 
listed in Table 3. However, use DIP-switch setting #1 in Table 3 since 
this setting has the highest overall offset/span adjustment capabilities. 
Enable DP2 via SW5 then apply 4mA and adjust R3 so the display 
reads “0.00”. Apply 20mA and adjust R7 so the display reads “15.99”. 
Apply 4mA and adjust R3 until the display reads “4.00”. Apply 20mA 
and check to see that the display reads “19.99” or just overranges 
(“1—“). Repeat adjustment procedure if necessary.

1. 

  Set R3 fully counterclockwise (minimum offset position) and R7 fully 

clockwise (minimum differential span position), roughly 22 turns.

2.

   Subtract 040 from 200 to yield a differential value of 160; use this value 

to select DIP-switch setting #5 in Table 3. Enable decimal point DP3 by 
placing SW6 to the ON position.

3. 

  Set the transmitter’s output to 4.0mA and carefully adjust R3 clockwise 

until the meter’s display reads “000”.

4.

   Set the transmitter’s output to 20.0mA and adjust R7 counterclock- 

wise until the meter’s display reads “16.0”.

5.

   Set the transmitter back to 4.0mA and slowly adjust R3 clockwise until  

the display reads “04.0”. Reapply 20.0mA and the display should now  
read “20.0”. Repeat steps 3, 4 and 5 to make sure the adjustments did  
not affect one another.

Examples (DMS-20PC-4/20P-Positive Model)

Table 3. DMS-20PC-4/20P (Positive Reading Model) 
DIP-Switch Settings

Differential Range   4mA Input 

 20mA Input 

Display Reading 

SW1  SW2  SW3

Table 4.  Decimal Point Settings

 

SW4 SW5 SW6

 DP1  DP2  DP3

  1

.   800-1400 

 

900 

 

1700 

 

Off 

Off 

Off

 2. 

   500-800 

 

850 

 

1350 

 

On 

Off 

Off

 3.

   350-500 

 

800 

 

1150 

 

Off 

On 

Off

 4.

   250-350 

 

750 

 

1000 

 

Off 

Off 

On

 5.

   150-250 

 

750 

 

900 

 

On 

On 

On

fully clockwise (roughly 22 turns) to their minimum offset/minimum span 
positions, respectively. 

The next step is to calculate the required display differential-reading; this 
is accomplished by subtracting the desired 4mA display reading from 
the desired 20mA display reading, disregarding decimal points. Then, 
using the calculated differential display-reading to select the appropriate 
DIP-switch setting # from Table 3, confi gure DIP-switches SW1, SW2, and 
SW3 accordingly. Make certain that the DIP-switch’s small actuators are 
fi rmly engaged in their fully-ON or fully-OFF positions.

The procedure below describes how to calibrate the meter for an applica-
tion which the DMS-20PC-4/20P easily accommodates: displaying the 
output of a 4-20mA transmitter, that is, “04.0” with a 4mA input and “20.0” 
with a 20mA input.

Отзывы: