Electrical Wiring
Chapter 3
3.2 Electrical Wiring
The Munters Drive fan ships configured for simple ON/OFF control. When electrical power is applied to
the main cable the fan will start and run at full speed.
See Figure 9A .
To operate the Munters Drive On/Off with a control, Slide the ‘ON’ switch, located on the circuit board in
the junction box, away from the ON position. Now wire an ‘ON’ command from the ‘COMMON’ terminal
to the input relay in the control and from the output of the control relay to the ‘RUN’ terminal in the junction
box.
See Figure 9A & 9B.
When making connections to junction box, be sure to use the supplied watertight fittings with only 1 cable
per fitting. If watertight fittings are not used or if 2 cables or more are in 1 watertight fitting, equipment
failure from water damage will not be covered under warranty. If 2 or more cables are used in 1
watertight fitting, they must be sealed on both sides of junction box wall to prevent water infiltration.
‘ON’ Switch
Figure 9A
Default Operation Full Speed
Junction Box
‘ON’ Switch