Target: Set the desired temperature.
Heat: Set the temperature to stop heat.
Tunnel: Set the temperature for tunnel ventilation to begin.
Alarm Low & High: Set average temperature alarm limits.
Floor heat: Set the temperature upon which the floor heat curve is based. Refer to
Variable Floor Heater | Set Definitions, page 22.
T.Hi: Set a high temperature alarm for Tunnel mode.
5. In
Manage > Alarm Setting
, set the Sensor Alarm (page 69).
NOTE:
Only Pig Mode supports variable floor heaters. To enable this function define an analog
output as a floor heater (refer to Analog Output, page 110).
6. If required set the:
o
Temperature Curve Help | Set Definitions, page 16
o
Radiant Heaters Help | Set Definitions, page 17
o
Variable Heater Help | Set Definitions, page 19
o
Variable Floor Heater | Set Definitions
o
Heat Cycle | Set Definitions
, page
Error! Bookmark not defined.
3.1.1
T
EMPERATURE
C
URVE
H
ELP
|
S
ET
D
EFINITIONS
While viewing the Temperature Curve menu: Press
HELP
, select SET, and press
ENTER
.
•
Temperature Curve Offset: Adjusts all temperature curves by this amount. You can use this to
temporarily adjust all temperatures up or down for special circumstances. The curve appears in
the
, and you can use the
ENTER and Up
or
ENTER and Down
hot key
combinations to change the offset.
•
Set Temp. Change Reminder (Diff): Sets the change in set temperature that triggers a
reminder for you to set backup thermostats. Often producers forget to set backup thermostats as
their birds grow from baby chicks to market age, so the Farm Premiumreminds you. When you
press Enter to acknowledge the reminder, the Farm Premium logs it in the Table of Events.
•
Target Temp. Band: The size of the target temperature zone. This "Happy Zone” is between
Target Temperature and (Target Tempe Band).
•
Heater Temp. Band: Heaters turn on at ‘Band’ degrees below Heat, and turn off at the Heat
Temperature.
NOTE:
Heaters operate at minimum level only; however, Radiant Heaters can operate at any
temperature or level below Tunnel.
•
Cool Down Factor (%): Minimum percentage correction towards target during each increase
. If average temperature does not improve by this amount, the Farm
Premium increases ventilation by one level.
SYSTEM PARAMETERS
TEMPERATURE CURVE
Temperature Curve Offset
Set Temp. Change Reminder (Diff)
Target Temp. Band
Heater Temp. Band
Cool Down Factor (%)
Cool Down Fast Response (Deg.)
Min Vent Below Heat Temp By:
Non Brood Area Diff. From Heat
0.0
3.0
1.5
1.0
15
3.0
ZONE
-3.0