Installation
13
DryCool HD Operator and Maintenance Manual
P00960167-1
Figure 6
shows how the unit draws return air from the common space or a ventilated closet and discharges the
dehumidified air back into the space.
Figure 6: Installation for Stand Alone Space
The DRYCOOL™ HD requires mounting of the remote humidistat away from the discharge in an
area that is representative of the larger space. As with all of the installation configurations of a unit, the
reactivation air still needs to be ducted to and from outdoors as shown here.
3.7. Humidistat Installation Requirements
Install the remote humidistat in a central area of the structure where it will sense the relative humidity of the
structure accurately. Do not install the humidistat where it may not accurately sense the relative humidity such
as near HVAC supply registers, near exterior doors, or near a pool or spa. The installer must supply the
wiring between the dehumidifier unit and the humidistat. Be sure to safely route the control wires to prevent
damage during installation. Be careful not to cross wires when connecting the DRYCOOL™ HD and
humidistat or damage to the transformer may result.
The humidistat of the DRYCOOL™ HD is powered by a low voltage circuit and must NEVER contact or be
connected to a high voltage circuit. The control wires leaving the unit and the humidistat are color coded to
prevent confusion. Be sure to consult the electrical schematic in this manual or the front panel of the unit before
making the control connections.
Please
NOTE
: Humidistat is not included. If purchased from Munters the humidistat will be supplied loose with
dehumidifier.