Please refer to the following figures to install.
17
.
INSTALL ELECTRIC THROTTLE PART
Connective Pipe 1
Connective Pipe 2
Fig.16-1
Fig.17-1
●
●
●
16
.
TROUBLE SHOOTING
For 200T1 unit, two mainboards in the electric control
should set the code ENC1 to 8;
For 250T1 unit, a mainboard in the electric control should
set the code ENC1 to 8; the other one should set the code
ENC1 to 9;
For 280T1 unit, two mainboards in the electric control
should set the code to 9.
For the same indoor unit, every mainboard must be differ-
ent indoor unit addresses and network addresses.
When using central controller to control the indoor unit,
please pay attention to the address setting, as the 200T1,
250T1 and 280T1 units have two or more mainboards. We
suggest setting the neighbor address for the mainboards
in the same indoor unit. When using a central controller for
controlling, mainboards in the same unit must be opened
and closed at the same time, for avoiding the unexpected
incident.
Table.16-1
NO. Type
Contents
Digital LED display
Remarks
The evaporator
sensor check
point is abnomal
or room temp.
sensor is
abnormal.
Indoor/outdoor unit
communication
is abnormal.
Outdoor unit
abnormal
Water level switch
is abnormal
Mode conflict
Error code
“H1,H2,H3,
E2,E3 or E4”
Error code
“E1”
Error code
“Ed”
Error code
“EE”
Error code
“E0”
After the malfunctions
disappear, it restores
automatically.
After the malfunctions
disappear, it restores
automatically.
After the malfunctions
disappear, it restores
automatically.
If the malfunctions
can’t be solved in
three min. all the
indoor alarm lamps
flash at 0.5Hz.Turn
off the power to restore.
When the indoor unit
turns to heating mode
or is turned off, the
alarm will disappear.
1
2
3
4
5
Malfun-
ction
Malfun-
ction
Malfun-
ction
Malfun-
ction
Alarm
7
6
Alarm
EPPROM error
The indoor unit
without an add-
ress when it is
first time electri-
fied
Malfun-
ction
Error code
“E7”
After the malfunctions
disappear, it restores
automatically.
Error code
“FE”
After the malfunctions
disappear, it restores
automatically.
SW7
ON
1 2
SW7
ON
1 2
ON
ON
SW7 Definition
0/1 Definition
SW6
ON
1 2 3
SW6
ON
1 2 3
SW6
ON
1 2 3
1 means old display panel
1 means auto air blow under
auto mode (reserved)
non-auto mode (reserved)
reserved
standard
configuration
last unit of
the network
means 0
means 1
SW6 Definition
CAUTION
Please adjust the code ENC1 to the suitable position (both
system A and B should be adjusted for 200T1, 250T1 and
280T1 indoor unit).
0 means new display panel
0 means auto air blow under
PRE-DEF indicator(cooling and heating type)
or fan only indicator(cooling only type)
Infrared signal receiver
Operation lamp
Timer indicator
Alarm indicator
Temporary button
Digital LED display
maintenance of motor
˖
0 1 2
F
3
E
4
D
5
C
6
B
7
A
89
Installation manual
Duct 100% fresh air
18
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW 5 Definition
00 means temp. compensation value
is 6
ć
under heat mode (reserved)
01 means temp. compensation value
is 2
ć
under heat mode (reserved)
10 means temp. compensation value
is 4
ć
under heat mode (reserved)
11 means temp. compensation value
is 8
ć
under heat mode (reserved)