Field procurement(M10)
Washer (attached)
Tighten(double nut)
(Securing the hanger bracket)
Inset
Washer fixing plate (attached)
(Securing the hanger bracket)
Fix screw of end of piping at the corner of
drainage trough
Pager pad for
installation
Screw (attached)
Fix paper pad for installation
Vinyl tube
Water level
Center of ceiling opening
Indoor unit installation
1.Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt.Be sure to fix it securely by using a nut and washer from the upper
and lower sides of the hanger bracket.the washer fixing plate
=
will prevent the washer from falling.
Refer to the paper pad for installation
=
for ceiling opening demension.
The center of the ceiling is indicated on the paper pad for installation,the center of the unit is indicated on the label
attached to the unit and on the paper pad for installation.
Fix the paper pad to the unit with screws
=
(
3)
3.Refer to diagram 3, adjust the unit.to the right position for installation.
4.Check if the unit is horizontally level.
The indoor unit is equipped with a built-in drainage pump and float switch.at each of the unit’s 4 corners,verify that
it is level by using a water level or a water filled vinyl tube.(If the unit is tilted against condensate flow,the float
switch my malfunction and cause water to drip.)
5.Remove the washer fixing plate
=
used for preventing the washer from falling and tighten the upper nut.
6.Remove the paper pad for installation
=
.
Indoor unit installation
Warning
Tighten the nut to prevent the unit from falling.
Indoor unit installation
27