7. Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ
6.35 (1/4”)
Φ
9.52 (3/8”)
Φ
12.7 (1/2”)
Formula
V=11g/m×(L-5)
V=30g/m×(L-5)
V=60g/m×(L-5)
V:
Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
Service manual
Inverter HF
60
Содержание MUCR-HF
Страница 5: ...Part 2 Indoor Units Super Slim Cassette Type 6 Duct Type 20 Service manual Inverter HF 5 ...
Страница 11: ...2 Dimensions Model A H MUCSR 48 HF 287 317 287 317 MUCSR 60 HF Service manual Inverter HF 11 ...
Страница 12: ...3 Service Space 1000mm 1000mm 1000mm 1000mm Service manual Inverter HF 12 ...
Страница 13: ...4 Wiring Diagrams MUCSR 48 HF UI20605 MUCSR 60 HF UI20606 Service manual Inverter HF 13 ...
Страница 14: ...Airflowvelocity Service manual Inverter HF 5 Air Velocity and Temperature Distributions Reference Data 14 ...
Страница 19: ...10 Field Wiring MUCSR 48 HF UI20605 MUCSR 60 HF UI20606 MUECR 48 60 HF Service manual Inverter HF 19 ...
Страница 26: ...4 Wiring Diagrams MUCR 48 HF UI20601 MUCR 60 HF UI20602 Service manual Inverter HF 26 ...
Страница 32: ...10 Field Wiring MUCR 48 HF UI20601 MUCR 60 HF UI20602 MUECR 48 60 HF Service manual Inverter HF 32 ...
Страница 64: ... Part 5 1 Troubleshooting 65 Troubleshooting Service manual Inverter HF 64 ...
Страница 69: ...3 E3 malfunction Service manual Inverter HF 69 ...
Страница 70: ...4 E4 malfunction NOTA Revisar todas las sondas Service manual Inverter HF 70 ...
Страница 73: ...7 P1 malfunction Service manual Inverter HF 73 ...
Страница 74: ...8 P2 malfunction Service manual Inverter HF 74 ...
Страница 75: ...9 P3 malfunction Service manual Inverter HF 75 ...