40
temperature increases to above 230 degrees. Determine if you have water flow or if the
thermostat is continuously energized and correct the problem. Manually reset by pushing
the
S4/reset
button.
F06
Return temperature is too High
– This code comes if the return water temperature goes
above 230 degrees,
Remedy
– Let the Munchkin cool down then manually push the reset button and see if the
temperature on the return increases to above 230 degrees. Check piping and determine the
source of over heating and correct the problem. Manually reset by pushing the
S4/reset
button.
F09
This code will occur if the Munchkin control does not detect a flame.
The Munchkin
will make three attempts for ignition before the control will go into a lockout condition. The
Munchkin control will try to re-ignite after one hour and continue to try to ignite every hour.
Remedy
– Check the Flame Rod, Spark electrode or Hot Surface Igniter to see if they are in
good condition. If the flame rod or spark electrode has corrosion, then clean it and re-
ignite. Also, check spark gap of ¼” on the spark electrode. If the Hot Surface igniter has any
visible cracks, then replace it with a new Hot Surface Igniter. Check any flue blockage and
condensate blocks. Also, check the Gas supply (Check Part 3, Table 1 [pg. 9] for pipe sizes
and gas pressure settings) and correct problem if it is out of specification. Manually reset
by pushing the
S4/reset
button.
F10
This code appears if the flame is going out while the burner is on and this hap-
pens more then 4 times in one heat demand.
Remedy
– Check to see if the green light on your display is out while the unit is running. If
the green light on the display either does not come on or goes out while running, read the
flame rod with a voltage meter to read the flame current. If it’s less than 1 micro-amp,
change or clean the flame rod. Also, check the Gas pressure while the unit is running to
determine if pressure is adequate. See Part 3, Gas Connection. If the gas pressure is too
low, correct the problem. Manually reset by pushing the
S4/reset
button.
F11
The flame detector circuit is seeing a flame signal while no flame is present.
Remedy
– Check the wiring to the Gas Valve. Check the flame rod and make sure it’s clean,
then manually reset
S4/Reset
button. If a lockout occurs, replace the board.
F13
Combustion fan running too slow.
The speed detected of the hall pulse signal is less than
70% of the desired fan speed for longer then 1 minute.
Remedy
– Check the Fan wiring. Manually reset by pushing the
S4/reset
button.
F14
The speed detected of the hall pulse is more then 130% of the desired fan speed
for longer then 1 minute when the fan should be on.
If the fan should be off and the
speed detected of the hall pulse output is more then 1500rpm and longer then 1 minute, this
code will appear.
Remedy
– Check Fan Wiring. Manually reset by pushing the
S4/reset
button.
F15
Air Pressure Switch is stuck open
. When in the pre-purge cycle, if the Air Switch does-
n’t close during the pre-purge high-speed mode after 1 minute, this code will appear.
Remedy
– Check the hose connection from the switch to the fan. Check to see if the inlet
is blocked. Check the air pressure switch contact. Adjust the switch, turn the center screw
counter clockwise in ¼ turn increments until switch clicks into closed position. Also check
to see if the fan is functional. Manually reset by pushing the
S4/reset
button.
F16
Air Pressure Switch is stuck closed.
If the Air Switch does not open while in the pre-
purge cycle, the unit will lockout after 1 minute.
Remedy
– Check the Air pressure switch for possible adjustment. Adjust the switch, turn
center screw clockwise in ¼ turn increments until switch clicks into open position if
necessary. Manually reset by pushing the
S4/reset
.
SERVICING