VersaTemp™ Water-to-Water Heat Pumps

MCA

WIRE SIZE (AWG) 75°

(3 Conductors/1 Conduit)

50

8

65

6

85

4

100

3

115

2

130

1

150

1/0

175

2/0

200

3/0

230

4/0

255

250 MCM

285

300 MCM

310

350 MCM

335

400 MCM

380

500 MCM

420

600 MCM

MCA

WIRE SIZE (AWG) 75°

(6 Conductors/2 Conduit)

510

250 MCM

570

300 MCM

620

350 MCM

670

400 MCM

760

500 MCM

800

600 MCM

Compressor Rated Load Amps (RLA) and Locked Rotor Amps (LRA) 

NOTE:

 RLA and LRA are for each compressor.

MCA = (1.25 x RLA1*) + RLA2 + RLA3+ RLA4 
Fuse Sizing: Maximum Overcurrent Protection (MOP), Type RK5 Fuse, or HACR Time Delayed 

Circuit Breaker 

MOP= (2.25 x RLA1*) + RLA2 
Where the MOP does not equal a standard size rating, the next larger size should be used. The 

MOP should not exceed 800 amps.

*NOTE

RLA1 = RLA of the largest compressor in the system; RLA2 , RLA3 & RLA4 = RLA of the 

other compressors in the system.
The total system Minimum Circuit Ampacity (MCA) shall not exceed 760A. Wire sizing is based 

on the National Electric Code (NEC) rating for 75°C copper wire, three wires per conduit. Wiring 

distance from branch circuit shall not exceed 100 feet.

System Wire & Fuse Sizing Specifications

(Applicable codes may require different wire sizing)

No. of 

Compressors

208/3/60

RLA/LRA

230/3/60

RLA/LRA

460/3/60

RLA/LRA

575/3/60

RLA/LRA

ARA020X

2

44/239

40/239

20/125

16/80

ARA030X

2

68/340

61/340

31/173

25/132

ARA060

2

N/A

N/A

60/310

48/239

RLA/LRA Per Compressor

Electrical  & Piping Information

Hot Water 

Side

Cold Water 

Side

Pressure Taps

Pressure Taps

Sensor

Wells

Sensor

Wells

Isolation

 Valves

Isolation 

Valve

Flow/DP

Switch

Flow/DP

Switch

Pump

Pump

Strainer

Items in Shaded Area Included 

with Chiller

Strainer

Fan Electrical Data

Consult as-ordered/as-built submittals for fan data. 

Recommended Water Piping

Multistack recommends a MINIMUM two to three minute water piping loop time.  

Содержание AirStack VersaTemp ARA 020X

Страница 1: ...1 VersaTemp Water to Water Heat Pumps 1 Air Cooled Template VersaTemp Water to Water Heat Pump with Auxiliary Air Cooled Coil Product Data Catalog ARA 020X 030X 060X Modules...

Страница 2: ...er to Water Heat Pumps Contents ARA Features Benefits 3 Model Number Nomenclature 4 5 General Information 6 7 Unit Dimensions Configurations 8 15 Electrical Piping Requirements 16 Guide Specifications...

Страница 3: ...ith refrigerant and are factory run tested prior to shipment on an AHRI certified test stand ARA modules are ETL listed according to UL Standard 1995 and CSA certified per Standard C22 2 236 Compresso...

Страница 4: ...Heat Pump 4 A Brazed SS V Other 5 A Cu tube Al fin B Cu tube Cu fin V Other 6 A None B Bronzeglow H Heresite E Electrofin S Standard V Other 7 E ECM Fans H High static L Single Fan V Other 8 R 410A P...

Страница 5: ...60 H 460 3 60 C 575 3 60 D 200 3 50 E 400 3 50 F 380 3 60 S 220 230 1 60 V Other Accessory Module ACP 2 H C 180 M B S C TankVolume Three digits 000 None Gallons Water Piping C Copper S Stainless P PVC...

Страница 6: ...4 1 Quantity 2 2 4 FanType Axial Axial Axial Fan Material Composite Composite Composite Air Flow Per Module per module 16 000 22 000 44 000 Air Cooled Coil ARA 020X ARA 030X ARA 060X Fin Material Alu...

Страница 7: ...sword levels provide three different access modes to the parameters read only for assistance edit for servicing and total access for the manufacturer Additional features include WiFi interface for tab...

Страница 8: ...s Typical Unit Dimensions ARA 020X Single Module Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recom mend pit installations Consult Mul...

Страница 9: ...ps Typical Unit Dimensions ARA 030X Single Module Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Страница 10: ...umps Typical Unit Dimensions ARA 030X Two Modules Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Страница 11: ...Dimensions Typical Unit Dimensions ARA 020X with ASP 020X Units CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recom mend pit installations Consult...

Страница 12: ...mps Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Multistack Representative for options Typical Uni...

Страница 13: ...umps Typical Unit Dimensions ARA 060X Two Modules Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Страница 14: ...mps Typical Unit Dimensions ARA 060X Four Modules Dimensions CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mul...

Страница 15: ...ps Dimensions Typical Unit Dimensions ARA 060X Multiwing Fans CLEARANCES No obstructions above fans Horizontal clearances as shown on drawing Multistack does not recommend pit installations Consult Mu...

Страница 16: ...the other compressors in the system The total system Minimum Circuit Ampacity MCA shall not exceed 760A Wire sizing is based ontheNationalElectricCode NEC ratingfor75 Ccopperwire threewiresperconduit...

Страница 17: ...structions for transporting rigging and assembly of modular chiller 1 06 WARRANTY A Manufacturer s equipment warranty shall be for a period of one 1 year from date of equipment start up or 18 months f...

Страница 18: ...essure reductions at 30 feet as compared to standard fan option ranges from 3 6 dBA H Central Control System 1 Scheduling of the various compressors shall be performed by a microprocessor based contro...

Страница 19: ...suction gas temperature 6 Low leaving evaporator water temperature B Failure of chiller to start or chiller shutdown due to any of the above safety cutouts shall be annunciated by display of the appr...

Страница 20: ...a professional water treatment specialist who is familiar with the operating conditions and materials of construction specified for the chiller s heat exchangers headers and associated piping Cycles...

Отзывы: