Page 1
UTC-421G
PV
= Process Value
SV
= Set Value
TEMPERATURE CONTROLLER
DISPLAY AND KEYS:
CONTROL METHOD:
DIMENSION:
OUTPUT SPECIFICATION:
POWER SUPPLY:
ENVIRONMENT CONDITION:
Display
Heating
Size
Keys
Cooling
Panel Cutout
Power Consuption
(VA Rating)
Relative Humidity
Protection Level
Relay
Output Signal
Supply Voltage
Operating Temp.
Relay Type
Rating
Upper: 4 digit, 7 segment, 0.56”
1) PID control with Auto-Tuning
Lower: 4 digit, 7 segment, 0.33”
2) ON-OFF control
48 (H) x 48 (W) x 95 (D) mm
100 to 270V AC, 50-60Hz
0°C to 55°C
UP to 95% RH
(non-condensing)
IP-65 (Front side) As per IS/IEC
60529 : 2001
1 Nos
12V DC, 30mA DC
(On-Off condition)
Relay parallel to SSR
1C/O (NO-C-NC)
10A, 230V AC / 28V DC
SET, INC, DEC, ENT
ON-OFF control
45 (H) x 45 (W) mm
4VA @ 230V AC MAX
Relay Output
SSR Drive Output
TECHNICAL SPECIFICATION
48
95
45
45
3
MECHANICAL INSTALLATION
TERMINAL CONNECTION
48
Outline Dimension (mm)
Panel Cutout
Dimension (mm)
6
6
6
8
8
7
7
7
3-Wire RTD
2-Wire RTD
Thermocouple
Install jumper
when using
2 Wire RTD
Sensor in
put
+
www.multispanindia.com
T/C
+
+
RTD
-
-
NC
C
Relay
NO
O/P
SSR
100
270V AC
1
2
3
4
5
L
N
6
7
8
9
10
~
50/60 HZ
4VA
Sensor Input
Input Types
Resolution
Indication
Input
Range
0 to 600°C
0.0 to 400.0°C
0 to 1200°C
-50 to 400°C
0.0 to 500.0°C
-50.0 to 400.0°C
J
J.1
K
PT-100
K.1
PT.1
J,K,PT-100 = 1°C
±1% of FSD ± 1°C
J.1,K.1,PT.1 = 0.1°C
INPUT SPECIFICATION:
Accuracy
UTC 421G
!
Made in India
Display Color
:
Upper : White Or Red
Lower : Green