background image

Page 1

UTC-421G

PV

 = Process Value

SV

 = Set Value

TEMPERATURE CONTROLLER

DISPLAY AND KEYS:

CONTROL METHOD:

DIMENSION:

OUTPUT SPECIFICATION:

POWER SUPPLY:

ENVIRONMENT CONDITION:

Display

Heating

Size 

Keys

Cooling

Panel Cutout

Power Consuption
(VA Rating)

Relative Humidity

Protection Level

Relay

Output Signal

 Supply Voltage

 Operating Temp.

Relay Type

Rating

Upper: 4 digit, 7 segment, 0.56” 

1) PID control with Auto-Tuning

Lower: 4 digit, 7 segment, 0.33” 

2) ON-OFF control

48 (H) x 48 (W) x 95 (D) mm

100 to 270V AC, 50-60Hz

0°C to 55°C

UP to 95% RH 
(non-condensing)

IP-65 (Front side) As per IS/IEC
60529 : 2001

1 Nos

12V DC, 30mA DC 
(On-Off condition)

Relay parallel to SSR

1C/O (NO-C-NC)

10A, 230V AC / 28V DC

SET, INC, DEC, ENT

ON-OFF control

45 (H) x 45 (W) mm

4VA @ 230V AC MAX

Relay Output

SSR Drive Output

TECHNICAL SPECIFICATION

48

95

45

45

3

MECHANICAL INSTALLATION

TERMINAL CONNECTION

48

Outline Dimension (mm)

Panel Cutout 
Dimension (mm)

6

6

6

8

8

7

7

7

3-Wire RTD

2-Wire RTD

Thermocouple

Install jumper 
when using 
2 Wire RTD

Sensor in

put

+

www.multispanindia.com

T/C

+

+

RTD

-

-

NC

C

Relay

NO

O/P

SSR

100  
270V AC
    

1

2

3

4

5

L

N

6

7

8

9

10

~

 

50/60 HZ
4VA

Sensor Input

Input Types

Resolution

Indication

Input  

Range

0 to 600°C 

0.0 to 400.0°C 

0 to 1200°C 

-50 to 400°C 

0.0 to 500.0°C 

-50.0 to 400.0°C 

J.1 

PT-100 

K.1 

PT.1 

J,K,PT-100 = 1°C

±1% of FSD ± 1°C

J.1,K.1,PT.1 = 0.1°C

INPUT SPECIFICATION: 

Accuracy

UTC 421G

!

Made in India

   Display Color

:

   Upper : White Or Red
   Lower : Green 

Отзывы: