Factory Setting
FACTORY SETTING
PARAMETER
IT
CT ( For PID)
OFFSET
PB
DT
HYSTERESIS-1
MR
VALUES
125
15 SEC.
200
30
3°C
0
0
SR.
2
4
1
3
5
6
7
www.multispanindia.com
Page - 3
Password Message
IF PID SELECTED
IF ON-OFF SELECTED
Proportional
Band
Integral
time
Derivative
time
Cycle Time
Manual Reset
TO ENTER CONTROL
PARAMETER
SETTING, ENTER “37”
SET
SET
Press key
to Save & Exit
Press key
to Save & Exit
Hysteresis
TC-49P
PID AUTO-TUNING
Press key for 6 sec to start/stop
PID auto-tuning
PV
Off-set correction
-10°C to 10°C
IT
CT
0 To 999
4 Sec To 99 Sec
Hysteresis
1°C to 10°C
DT
MR
0 To 999
-10°C to 10°C
PB
Sr.
1
2
3
4
5
6
7
0 To 999
Parameter
Range for J,K
SET
SET
yes : press key to apply factory set
values as shown in table.
nO : press key to escape
from factory setting.
Press + key
for 3 sec
Control Parameter
Press Key
SET
SET