2)

 

Initially  when  temperature  reaches  to  the  Set  value  decided,  during  that  period  RELAY  1  (R1) 
turns ON. When it crosses to the Set value then RELAY R1 becomes OFF. Again when it reaches 

SEt  - HYS

 where Hysteresis is fixed 2°C it will turns ON again RELAY (R1). 

3)

 

Here, Relay R1 is for controlling purpose. It operates only when temperature reaches to the set 
point. 

4)

 

By pressing both           &              keys one can see on the lower display  which particular rate or 
which particular hold time is going on. 

5)

 

Every Higher stage set point is always greater than all its lower stage set point except the last 
stage (9) set point. The ninth stage set point can set to any value from 0 to 1200 °C. 

 

Note # 1

:  

When you operate this unit first time, you can freely play with                                     key 

to understand key operations, previously set parameter will remain unaffected as long as you 
don’t press           key. 

 