Multispan Control Instruments Pvt Ltd
72/B, Phase 1, GIDC Estate, Vatva, Ahmedabad-382445, Gujarat, India.
www.multispanindia.com
+91-9978991483
AVH 13N
User Manual
ENVIRONMENT CONDITION:
INPUT:
Direct Voltage AC
30 to 300V(L - N)
50 to 500V(L - L)
Burden
Voltage AC
Current AC
Burden
Primary CT Ratio
Secondary Current AC
Overload
Frequency
Up to 6A continuous
40.0 to 80.0 Hz
< 0.2VA
5 to 4000 Amp selectable
< 0.2VA
0.1A to 5 Amp Direct
3 Phase - 4 Wire
(Network Selection)
Supply Voltage
230V AC, 50 Hz
Power Consuption
4VA @ 230 AC MAX
AUXILIARY SUPPLY:
Size (mm)
Panel Cutout (mm)
96 (H) X 96 (W) X 52 (D) mm
92 (H) X 92 (W) mm
DIMENSION:
Display
3 Line, 4 Digit, 7 Seg 0.56”,RED LED
Keys
RESET,SCRL/HOLD
DISPLAY AND KEYS:
Technical Specification
Protection Level
(As Per Request)
IP-65 (Front side) As per IS/IES
60529 : 2001
Operating Temperature
0°C To 55°C
Relative Humidity
Up to 95% RH Non Codensing
Terminal Diagram
www.multispanindia.com
1
2
3
4
7
8
9
12
13
14
10
11
5
16
17
18
19
20
6
15
S1
S1
S1
S2
S2
S2
R
Y
B
V
R
V
Y
V
B
N
System :
3 Ph-4W
Accuracy Class:
0.5
Range
Current:
0.1 To 5A AC
Voltage(P-P) :
50-500V AC
(P-N) :
30-300V AC
L
N
50 Hz, 4VA
2 0V
3
AC
!
Made in India
CAT III
Page 5
Page 6
Continue...
Page 7
Page 8
Continue...
Reset KWH
RESET
METER
MFM
AVH 13N
Freq
2 3 0 2
.
2 3 1 0
.
2 2 9 3
.
RESET
METER
MFM
AVH 13N
Freq
R E S T
U N i T
Press Key for 8 Sec.
to Reset KWH
RESET
Press Key for
Reset KWH
SCRL
HOLD
Parameters
Parameter Display
Line CURRENT ( ~A )
0.100
-
5.0
00
A
(Direct without CT)
050.0 - 500.0V
30.0
-
3
00.0V
0.000 -
4000
KW
0.000 - 999999 KWh
0
.100
-
1.000
PF
0.000 - 9999 KVA
40.
0 -
80.0
Hz
Line Voltage (Phase-to-Phase)
Phase Neutral Voltage ( P-N )
Active Power ( KW ) Total
Active Energy ( Kwh )
Power Factor ( PF ) Average
Apparent Power ( KVA )
Frequency ( Freq )
Measurement Range