PAGE 40 — DCA-45SSIU2 — OPERATION AND PARTS MANUAL (STD) — REV. #7 (06/13/07)
DCA-45SSIU2 — PRE-SETUP
When connecting battery do the following:
1.
NEVER
connect the battery cables to the battery
terminals when the
ignition
switch is in either the
Pre-
Heat, RUN, or START
position.
ALWAYS
make sure
that the ignition switch is in the
STOP
position when
connecting the battery.
2. Place a small amount of battery terminal treatment
compound around both battery terminals. This will ensure
a good connection and will help prevent corrosion around
the battery terminals.
Figure 43. Battery Connections
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
:
ALWAYS
disconnect the negative
terminal
FIRST
and reconnect
negative terminal
LAST
.
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
:
Inadequate battery connections may cause
poor starting of the generator, and create
other malfunctions.
Alternator
The polarity of the alternator is negative grounding type. When
an inverted circuit connection takes place, the circuit will be
in short circuit instantaneously resulting the alternator failure.
DO NOT
put water directly on the alternator. Entry of water
into the alternator leads an electrolyte corrosion causing an
alternator failure.
Before charging the battery with an external electric source,
be sure to disconnect the battery cables.
Wiring
Inspect the entire generator for bad or worn electrical wiring
or connections. If any wiring or connections are exposed
(insulation missing) replace wiring immediately.
Piping and Hose Connection
Inspect all piping, oil hose, and fuel hose connections for
wear and tightness. Tighten all hose clamps and check hoses
for leaks.
If any hose (
fuel
or
oil
) lines are defective replace them
immediately.
If the battery cable is connected
incorrectly, electrical damage to the
generator will occur. Pay close
attention to the polarity of the
battery when connecting the
battery.
NOTE
Battery
This unit is of negative ground
DO NOT
connect in reverse.
Always maintain battery fluid level between the specified
marks. Battery life will be shortened, if the fluid level are not
properly maintained. Add only distilled water when
replenishment is necessary.
DO NOT
over fill. Check to see whether the battery cables
are loose. Poor contact may result in poor starting or
malfunctions.
Always
keep the terminals firmly tightened.
Coating the terminals with an approved battery terminal
treatment compound. Replace battery with only
recommended type battery. The battery type used in this
generator is BCI Group 27.
The battery is sufficiently charged if the specific gravity of
the battery fluid is 1.28 (at 68° F). If the specific gravity
should fall to 1.245 or lower, it indicates that the battery is
dead and needs to be recharged or replaced.
Battery Cable Installation
ALWAYS
be sure the battery cables (Figure 43) are properly
connected to the battery terminals as shown below. The
RED
cable is connected to the positive terminal of the battery,
and the
BLACK
cable is connected to the negative terminal
of the battery.
Содержание Power WHISPERWATT DCA-45SSIU2
Страница 2: ...PAGE 2 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 Diesel engine exhaust and some of ...
Страница 3: ...DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 PAGE 3 NOTE PAGE ...
Страница 9: ...DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 PAGE 9 NOTE PAGE ...
Страница 23: ...DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 PAGE 23 DCA 45SSIU2 GENERATOR DECALS ...
Страница 60: ...PAGE 60 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 DCA 45SSIU2 GENERATOR ASSY GENERATOR ASSY ...
Страница 72: ...PAGE 72 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 DCA 45SSIU2 BATTERY ASSY BATTERY ASSY ...
Страница 74: ...PAGE 74 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 DCA 45SSIU2 MUFFLER ASSY MUFFLER ASSY ...
Страница 76: ...PAGE 76 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 DCA 45SSIU2 FUELTANK ASSY FUEL TANK ASSY ...
Страница 100: ...PAGE 100 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 ENGINE MOUNTING ASSY ENGINE MOUNTING ASSY ...
Страница 102: ...PAGE 102 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 INLET MANIFOLD ASSY INLET MANIFOLD ASSY ...
Страница 106: ...PAGE 106 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 VENTILATION ASSY VENTILATION ASSY ...
Страница 116: ...PAGE 116 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 FUEL INJECTION ASSY FUEL INJECTION ASSY ...
Страница 130: ...PAGE 130 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 BATTERY RELAY ASSY BATTERY RELAY ASSY ...
Страница 132: ...PAGE 132 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 STARTER COMP ASSY STARTER COMP ASSY ...
Страница 138: ...PAGE 138 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 GOVERNOR COMP ASSY GOVERNOR COMP ASSY ...
Страница 142: ...PAGE 142 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 FEED PUMP ASSY FEED PUMP ASSY ...
Страница 146: ...PAGE 146 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 COUPLING ASSY COUPLING ASSY ...
Страница 150: ...PAGE 150 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 AIR DUCT ASSY AIR DUCT ASSY ...
Страница 152: ...PAGE 152 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 FUEL SEDIMENTER ASSY FUEL SEDIMENTER ASSY ...
Страница 154: ...PAGE 154 DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 ISUZU 4BG1 CLUTCH ASSY CLUTCH ASSY ...
Страница 159: ...DCA 45SSIU2 OPERATION AND PARTS MANUAL STD REV 7 06 13 07 PAGE 159 NOTE PAGE ...