DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22) — PAGE 35
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available for many different
applications. Voltages are selected by using the
voltage
change-over board
(Figure 20). To obtain some of the
voltages as listed in Table 8 (see below) will require a fine
adjustment using the
voltage regulator (VR)
control knob
located on the control panel.
Voltage Change-Over Board
The
voltage change-over board
inside the control box, behind the generator control panel.
This board has been provided for ease of voltage selection.
Figure 20. Voltage Change-Over Board
X
Y
Z
O
U
U
1
2
V
V
2
1
W
W
2
1
JUMPER
6 PLACES
1
2
3
4
5
6
WARNING
NEVER
attempt to place jumper plates on the
voltage
change-over board
while the generator is in operation.
There exists the possibility of
electrocution
,
electrical
shock
,
or burn
,
which can cause severe bodily harm
or even death!
Table 8. Voltages Available
UVWO Output
Terminal Lugs
Voltage Change-Over Board
3-Phase 240/139V Position
Voltage Change-Over Board
3-Phase 480/270V Position
3Ø
Line-Line
208V
220V
240V
416V
440V
480V
1Ø Line-Neutral
120V
127V
139V
240V
254V
277V
Maximum Amps
Table 9 shows the
maximum
amps the generator can
provide.
DO NOT
exceed the maximum amps as listed.
Table 9. Generator Maximum Amps
Rated Voltage
Maximum Amps
1Ø 120 Volts
888.9 × 2 amps (4 wire)
1Ø 240 Volts
444.4 amps (4 wire)
3Ø 240 Volts
962.3 amps
3Ø 480 Volts
481.1 amps
Main Line Circuit
Breaker Rating
1,000 amps