DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22) — PAGE 31
OUTPUT TERMINAL PANEL FAMILIARIZATION
120 VAC GFCI Receptacles
There are two 120 VAC, 20-amp GFCI (Duplex Nema
5-20R) receptacles provided on the output terminal panel.
These receptacles can be accessed in any
voltage
change-over board
position. Each receptacle is protected
by a 20-amp circuit breaker. These breakers are located
directly above the GFCI receptacles. Remember the load
output (current) of both GFCI receptacles is dependent on
the load requirements of the U, V, and W output terminal
lugs.
Pressing the
reset
button resets the GFCI receptacle after
being tripped. Pressing the
test button
(See Figure 14) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
Reference the maintenance section in this manual for
further testing of the GFCI receptacle.
Figure 14. 120 VAC GFCI Receptacle
Twist-Lock Dual-Voltage 240/139 VAC Receptacles
There are three 240/139V, 50-amp, auxiliary twist-lock
(CS-6369) receptacles (Figure 15) provided on the output
terminal panel. These receptacles can
only
be accessed
when the voltage change-over board is configured for
single-phase 240/120V
application.
NOTICE
It is recommended that the GFCI receptacles be tested
when the generator is initially uncrated. The receptacles
should then be tested daily at startup.
TEST
BUTTON
RESET
BUTTON
STATUS
LED
Figure 15. 240/139V Twist-Lock
Auxiliary Receptacles
Each auxiliary receptacle is protected by a 50-amp circuit
breaker. These breakers are located directly above the
GFCI receptacles. Remember the load output (current) on
all three receptacles is dependent on the load requirements
of the
output terminal lugs
.
The
output terminal lugs
are protected by a protective
cover (Figure 16). Unscrew the securing bolts (8) and
remove the cover to gain access to the output terminal lugs.
After the load wires have been securely attached to the
output terminal lugs, reinstall the protective cover, and
reinstall the retaining bolts.
Figure 16. Protective Terminal Cover
(UVWO Terminal Lugs)
SINGLE-PHASE
240/139 VAC
50-AMP OUTPUT
CS-6369
TWIST-LOCK
RECEPTACLES
RETAINING
BOLT
PROTECTIVE
TERMINAL COVER