DCa125USI3CaN 60 hz geNerator • operatIoN aND partS maNUal — rev. #2 (09/24/13) — page 25
LOAD APPLICAtION
SINgle phaSe loaD
Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage, frequency,
and voltage requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require
130—150% more wattage than the rating on the nameplate,
as the wattage is influenced by the efficiency, power factor
and starting system of the equipment.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 0.8. See Table 5 below
when connecting loads.
table 6. Cable Selection (60 hz, Single phase operation)
Current
in
Amperes
load in Watts
maximum allowable Cable length
At 100
volts
At 200
volts
#10 Wire #12 Wire #14 Wire #16 Wire
2.5
300
600
1000 ft.
600 ft.
375 ft.
250 ft.
5
600
1200
500 ft.
300 ft.
200 ft.
125 ft.
7.5
900
1800
350 ft.
200 ft.
125 ft.
100 ft.
10
1200
2400
250 ft.
150 ft.
100 ft.
15
1800
3600
150 ft.
100 ft.
65 ft.
20
2400
4800
125 ft.
75 ft.
50 ft.
CAUTION: Equipment damage can result from low voltage
NOTICE
If wattage is not given on the equipment’s name plate,
approximate wattage may be determined by multiplying
nameplate voltage by the nameplate amperage.
table 5. power Factor By load
type of load
Power Factor
Single-phase induction motors
0.4-0.75
Electric heaters, incandescent lamps
1.0
Fluorescent lamps, mercury lamps
0.4-0.9
Electronic devices, communication
equipment
1.0
Common power tools
0.8
three phaSe loaD
When calculating the power requirements for 3-phase
power use the following equation:
An inadequate size connecting cable which cannot carry the
required load can cause a voltage drop which can burn out
the appliance or tool and overheat the cable. See Table 6.
When connecting a resistance load such as an
incandescent lamp or electric heater, a capacity of up to
the generating set’s rated output (kW) can be used.
When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set’s rated output (kW)
multiplied by 0.6 can be used.
When connecting an electric drill or other power tools,
pay close attention to the required starting current
capacity.
When connecting ordinary power tools, a capacity of up to
the generating set’s rated output (kW) multiplied by 0.8 can
be used.
NOTICE
Motors and motor-driven equipment draw much greater
current for starting than during operation.
NOTICE
If 3Ø load (kVA) is not given on the equipment
nameplate, approximate 3Ø load may be determined
by multiplying voltage by amperage by 1.732.
DANGER
Before connecting this generator to any building’s
electrical system, a
licensed electrician
must install
an
isolation (transfer) switch
. Serious damage to
the building’s electrical system may occur without this
transfer switch.
Содержание DCA125USI3CAN
Страница 19: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 19 Notes...
Страница 51: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 51 Notes...
Страница 54: ...page 54 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 GENERATOR ASSY...
Страница 56: ...page 56 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 control box ASSY...
Страница 58: ...page 58 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 control box ASSY continued...
Страница 60: ...page 60 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 control box ASSY continued...
Страница 62: ...page 62 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 ENGINE AND RADIATOR ASSY...
Страница 68: ...page 68 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 OUTPUT TERMINAL ASSY...
Страница 70: ...page 70 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 BATTERY ASSY...
Страница 72: ...page 72 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 Muffler Assy...
Страница 74: ...page 74 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 FUEL TANK ASSY...
Страница 76: ...page 76 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 ENCLOSURE ASSY PART 1...
Страница 78: ...page 78 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 ENCLOSURE ASSY PART 1 continued...
Страница 80: ...page 80 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 ENCLOSURE ASSY PART 2...
Страница 82: ...page 82 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 ENCLOSURE ASSY PART 2 continued...
Страница 84: ...page 84 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 RUBBER SEALS ASSY...
Страница 91: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 91 notes...