2010-01-26
SPECIFICATIONS:
Input Voltage: 230VAC~50Hz +/-10%
Output Voltage: 13.6VDC, 207W/Alt.27.2V DC, 240W
Max Power: 207W/Alt. 240W
Current Limit: ca. 110% of Max. Current.
Standard: EN 60950, Class 1
Marking: CE
GENERAL INSTRUCTIONS.
Type 975 is for indoor use only and has to be installed in a rooms with good ventilation and
temperature between -5 to +35ºC
Charging batteries may under certain adverse conditions, generate harmful or explosive
gases. Please avoid open flames and sparks near a battery being charged
MAINS CONNECTION.
Main voltage(230VAC~50Hz):
N(neutral), L(live),
(ground)
Battery connection:
Fuse F1 to
+
1 ,and F3 to
-
4
Load connection:
F2 to +2 and +3, and F4 to -5 and -6(please see drawing
below).
NB! When ALARM RELAY is in OK connection, the relay is activated
and there is connection between C/NO.
To avoid unessesary alarm indications in places where the mains-supply
is unstable, you may delay the alarm function (see preset table).
Preset of DIP-switch:
1 2 3 4
x 0 0 x 0min. delay Alarm relay
x 1 0 x 5min. delay Alarm relay
x 0 1 x 10min. delay Alarm relay
x 1 1 x 30min. delay Alarm relay
x x x 1
Alarm function
on
when battery defect or not connected
1 x x x Battery Test each 24 hours
on
Battery will be connected earlier than 1min. after alarm indicated.
LED Indication:
LED1 LED2 LED3
RED GREEN Lit when REL2 is
activated
0 1 Situation
OK (
SituationOK)
1 0 Battery
fault
1010.. 1010..
Test routine
on
0 1010.. Mains off/Charger
fail or
1010.. 0 Battery
not
connected
0=off, 1=on, 1010..= blinking