INSTALLATION & OPERATING
MANUAL
CFFWA Universal Mount Fan Coils
12,000 – 60,000 BTUH
Figure 6
Figure 6
INSTRUCTIONS FOR
INSTALLING THE MOUNTING
BRACKETS AND UNIT
7. Carefully place fan coil into place and
align mounting holes on both sides of the
fan coil with the holes in the mounting
brackets. Secure unit with mounting
bolts.
Figure 6
8. Connections to the indoor unit are
flared connections for both the water
inlet and outlet to the fan coil.
Figure 7
9. Ensure tubing and fittings are in line
with another before tightening nut to
allow concentric seating of tube onto
flare nut as to prevent leakage. Ensure
the unit’s flared connections are
supported with a backup wrench when
removing or tightening flair nuts.
10. Insulate both the inlet and outlet
liquid solution lines to prevent
condensation leakage.
11. Connect the field drain line to the
clear drain tubing provided on the drain
pan of the fan coil. Ensure the drain line
has a ¼” of fall per foot. Insulate the
condensate drain line to prevent
condensate sweating.
Figure 8
Figure 7
Figure 8
-------- CAUTION -------
Care must be taken when
handling sheet metal. Sheet
metal parts have sharp edges
and could cause injury.