Description of Electrical Controls (continued)
Liquid Solution Temperature Control:
The liquid solution temperature control
is an adjustable microprocessor based temperature control. This control receives
temperature information from a thermistor located on the liquid solution supply
line. A liquid crystal display continually indicates liquid solution temperature. The
control is mounted inside the chiller cabinet.
Chiller Controls Sequence of Operation
When powered up the Multiaqua chiller system energizes the control transformer creating 24 vac control voltage.
First the pump bypass timer is energized and temporarily bypasses the flow switch, energizing the pump relay. The
If the liquid solution temperature controller is calling for cooling the control circuit is routed through the short cycle
pump then starts to move liquid solution through the piping system (in a properly filled and air purged system). The
movement of liquid solution from the pump discharge keeps the flow switch closed. After a 10 second delay the pump
contact opens, connecting the flow switch in series with the high and low pressure switches. The pump will now run
continually unless the power supply is interrupted, or the flow switch opens.
timer and the three safety switches (the flow, high and low pressure switches) to the compressor contactor. This will
energize the compressor(s) and condenser fan motors. The liquid solution controller will open at the user programmed
set point, causing the refrigerant short cycle timer to open it's contact for 5 minutes as it delays before resetting to the
closed position. This will de-energize the compressor. Power fluctuations will also initiate a 5 minute time delay. The
5 minute delay allows the refrigerant system a period for pressure equalization, protecting the compressor(s) from
short cycling.
The chiller temperature controller utilizes a thermistor to monitor the liquid solution temperature change. The
temperature is then compared to the set point and differential temperatures programmed into the control by the user.
The set point is the liquid solution temperature which will cause the control switch to open. For example: The control
set point is programmed at 44°F LWT with a 10°F differential, which opens the controller at 44°F LWT and closes at
54°F. The differential temperature is the number of degrees above set point temperature programmed into the
controller. If liquid solution temperature falls to the set point, the controller cycles the compressors off.
Chillers are shipped with the control set point adjusted to 44°F LWT and a 10°F differential. Liquid solution
temperature set point should not be set below 35°F.
65
Содержание CFFWA Series
Страница 1: ......
Страница 8: ...3...
Страница 14: ...Air Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC120 Air Cooled Chiller 9...
Страница 22: ...17...
Страница 35: ...Notes Banked Chiller Configuration Installing Multiaqua chillers in parallel is recommended 30...
Страница 39: ...34 MAC120 3 Ladder Wiring Diagram 380 460 3 50 60...
Страница 42: ...37 MAC120 2 Ladder Wiring Diagram 208 230 3 50 60...
Страница 43: ...38 MAC120 2 Wiring Diagram 208 230 3 50 60...
Страница 44: ...39 MAC120 2 L with Low Ambient Kit Wiring Diagram 208 230 3 50 60...
Страница 45: ...40 MAC120 1 Ladder Wiring Diagram 208 230 1 50 60...
Страница 46: ...41 MAC120 1 Wiring Diagram 208 230 1 50 60...
Страница 47: ...42 MAC120 1 L with Low Ambient Kit Wiring Diagram 208 230 1 50 60...
Страница 48: ...MAC120 CERTIFIED DRAWING 43...
Страница 62: ...57...
Страница 79: ...74 MAC060 3 Ladder Wiring Diagram 380 460 3 50 60...
Страница 80: ...75 MAC060 3 Wiring Diagram 380 460 3 50 60...
Страница 81: ...76 MAC060 3 L with Low Ambient Kit Wiring Diagram 380 460 3 50 60...
Страница 82: ...77 MAC036 048 060 2 Ladder Wiring Diagram 208 230 3 50 60...
Страница 83: ...78 MAC036 048 060 2 Wiring Diagram 208 230 3 50 60...
Страница 84: ...79 MAC036 048 060 2 L with Low Ambient Kit Wiring Diagram 208 230 3 50 60...
Страница 85: ...80 MAC036 048 060 1 Ladder Wiring Diagram 208 230 1 50 60...
Страница 86: ...81 MAC036 048 060 1 Wiring Diagram 208 230 1 50 60...
Страница 87: ...82 MAC036 048 060 1 L with Low Ambient Kit Wiring Diagram 208 230 1 50 60...
Страница 88: ...83 MAC036 048 060 CERTIFIED DRAWING...
Страница 103: ...97...
Страница 108: ...102...
Страница 119: ...113 MHCCW Without Electric Heat Wiring Diagram 208 230 1 50 60...
Страница 120: ...114 MHCCW With Electric Heat Wiring Diagram 208 230 1 50 60...
Страница 121: ...115 MHCCW Without Electric Heat Wiring Diagram 120 1 50 60...
Страница 122: ...116 MHCCW CERTIFIED DRAWING...
Страница 123: ...117 4 Pipe Heat Cool Fan Coil 12 000 36 000 BTUH Ceiling Concealed MHNCCW Chilled Hot Water...
Страница 140: ...134...
Страница 151: ...145 MHNCCW xx 01 Wiring Diagram 208 230 1 50 60...
Страница 152: ...146 MHNCCW xx 03 Wiring Diagram 120 1 60...
Страница 153: ...146...
Страница 154: ...147 MHNCCW CERTIFIED DRAWING...
Страница 155: ...148 2 Pipe Heat Cool Fan Coil 48 000 60 000 BTUH Ceiling Concealed MCCW Chilled Hot Water...
Страница 165: ...158...
Страница 176: ...169 MCCW xx 01 Wiring Diagram 208 230 1 50 60...
Страница 177: ...170 MCCW CERTIFIED DRAWING...
Страница 178: ...2 Pipe Heat Cool Fan Coil 9 000 36 000 BTUH Hi Wall Fan Coil 171 MHWW Chilled Hot Water...
Страница 194: ...187...
Страница 209: ...202 MHWW 09 H 1 MHWW 12 H 1 Wiring Diagram 208 230 1 50 60...
Страница 210: ...203 MHWW 18 H 1 Wiring Diagram 208 230 1 50 60...
Страница 211: ...204 MHWW 24 H 1 Wiring Diagram 208 230 1 50 60...
Страница 212: ...205 MHWW 36 H 1 Wiring Diagram 208 230 1 50 60...
Страница 213: ...206 MHWW CERTIFIED DRAWING...
Страница 214: ...2 Pipe Heat Cool Fan Coil 12 000 60 000 BTUH Universal Mount Fan Coil 207 CFFWA Chilled Hot Water...
Страница 231: ...223...
Страница 233: ...225...
Страница 237: ...229 INSTALLATION OPERATING MANUAL CFFWA Universal Mount Fan Coils 12 000 60 000 BTUH Piping Locations...
Страница 239: ...231 CFFWA xx 1 U Wiring Diagram 208 230 1 50 60...
Страница 240: ...232 CFFWA CERTIFIED DRAWING...
Страница 241: ...2 Pipe Heat Cool Fan Coil 18 000 60 000 BTUH With or Without Electric Heat 233 CWA2 Chilled Water Fan Coil...
Страница 257: ...249...
Страница 265: ...257 CWA2 00 Wiring Diagram 208 230 1 60...
Страница 266: ...258 CWA2 CERTIFIED DRAWING...
Страница 267: ...4 Pipe Heat Cool Fan Coil 24 000 60 000 BTUH 259 CWA4 Chilled Hot Water Fan Coil...
Страница 279: ...271...
Страница 287: ...279 CWA4 Wiring Diagram 120 1 60...
Страница 288: ...280 CWA4 CERTIFIED DRAWING...