Einheit Blindenergie L3 Induktiv 

              5 

kvar, Mvar 

Blindenergie L3 Kapazitiv 

 

Einheit Blindenergie L3 Kapazitiv 

kvar, Mvar 

Stromwandler Primär 

 

Stromwandler Sekundär 

 

Spannungswandler Primär 

 

Spannungswandler Sekundär 

 

Seriennummer 

 

Softwareversion 

 

 

unit reactive energy L3 inductive 

              5 

kvar, Mvar 

reactive energy L3 capacitive 

 

unit reactive energy L3 capacitive 

kvar, Mvar 

current transformer primary  

 

current transformer secondary 

 

voltage transformer primary 

 

voltage transformer secondary 

 

serial number 

 

software version 

 

 

Messwertabfrage mit MODBUS-TCP-Protokoll 

Die Messwerte des EZD-TCP können auch per MODBUS-TCP-Protokoll ausgelesen werden. 
Verbinden Sie den Zähler mit einem Crossover-LAN-Kabel (Zubehör) mit Ihrem PC oder mit 
dem  MODBUS-Master.  Die  Adressierung  des  EZD-TCP  erfolgt  über seine  IP-Adresse  (Port 
502). Das kleinste Intervall zum Auslesen der Messwerte sollte nicht kleiner als  1 Sekunde 
sein.  Die  Register  können  nur  gelesen  werden.  Es  werden  folgende  MODBUS-Befehle 
unterstützt: 
 
Code: 

0x03 

Read Holding Registers 

Code: 

0x08 

Diagnostic 

 
Bei  nicht  unterstützten  Befehlen  oder  falschen  Adressangaben  wird  eine  entsprechende 
Fehlermeldung ausgegeben. 
 

Achtung! Es können maximal 55 Register (110 Byte) pro Abfrage ausgelesen werden

 

Datenformate 

INT16/UINT16 = 2 Byte, signed/unsigned (high vor low Byte) 
INT32/UINT32 = 4 Byte, signed/unsigned (high vor low Byte, low Word vor high Word) 
 
Messwertliste 

Adresse Hex (Dec) 

Messwert 

Typ 

Einheit 

Auflösung 

0x0001 (01) 

Spannung L1-N 

  UINT32 

             V 

              0,01 

0x0003 (03) 

Spannung L2-N 

UINT32 

0,01 

0x0005 (5) 

Spannung L3-N 

UINT32 

0,01 

0x0007 (7) 

Spannung L1-L2 

UINT32 

0,01 

0x0009 (9) 

Spannung L2-L3 

UINT32 

0,01 

0x000B (11) 

Spannung L1-L3 

  UINT32 

             V 

             0,01 

0x000D (13) 

Strom L1 

UINT32 

0,01 

0x000F (15) 

Strom L2 

UINT32 

0,01 

0x0011 (17) 

Strom L3 

UINT32 

0,01 

0x0013 (19) 

Strom N 

UINT32 

0,01 

0x0015 (21) 

Frequenz L1 

UINT16 

Hz 

0,01 

0x0016 (22) 

Frequenz L2 

UINT16 

Hz 

0,01 

0x0017 (23) 

Frequenz L3 

UINT16 

Hz 

0,01 

0x0018 (24) 

Wirkleistung L1 

INT32 

Watt 

0x001A (26) 

Wirkleistung L2 

INT32 

       Watt 

             1 

0x001C (28) 

Wirkleistung L3 

INT32 

Watt 

0x001E (30) 

Wirkleistung Summe 

INT32 

Watt 

0x0020 (32) 

Blindleistung L1 

INT32 

var 

0x0022 (34) 

Blindleistung L2 

INT32 

var 

0x0024 (36) 

Blindleistung L3 

INT32 

var 

0x0026 (38) 

Blindleistung Summe 

INT32 

var 

0x0028 (40) 

Scheinleistung L1 

INT32 

VA 

0x002A (42) 

Scheinleistung L2 

INT32 

VA 

0x002C (44) 

Scheinleistung L3 

INT32 

VA 

0x002E (46) 

Scheinleistung Summe 

INT32 

VA 

0x0030 (48) 

Leistungsfaktor L1 

INT16 

 

0,01 

0x0031 (49) 

Leistungsfaktor L2 

INT16 

 

0,01 

0x0032 (50) 

Leistungsfaktor L3 

INT16 

 

0,01 

0x0033 (51) 

Leistungsfaktor Summe 

INT16 

 

0,01 

Measured value queries with the MODBUS-TCP protocol 

The  measured  values  of  the  EZD-TCP  can  be  read  out  using  the  MODBUS-TCP  protocol. 
Connect the counter with a crossover-LAN cable (accessory) to your PC or with the MODBUS 
master. The addressing of the EZD-TCP is via its IP address (Port 502). The smallest interval 
for reading out the values should not be less than 1 second. The registers can only be read 
out. It supports the following Modbus commands: 
 
 
Code: 

0x03 

Read Holding Registers   

 

Code: 

0x08 

Diagnostic 

 
For  non-supported  commands  or  incorrect  address  information,  an  appropriate  error 
message is issued. 
 

Caution! A maximum of 55 registers (110 bytes) can be read out per query.

 

 

Formats 

INT16/UINT16 = 2 byte, signed/unsigned (high before low byte) 
INT32/UINT32 = 4 byte, signed/unsigned (high before low byte, low word before high word) 
 
measured values list 

Adresse Hex (Dec) 

Messwert 

Typ 

Einheit 

Auflösung 

0x0001 (01) 

voltage L1-N 

  UINT32 

             V 

            0,01 

0x0003 (03) 

voltage L2-N 

UINT32 

0,01 

0x0005 (5) 

voltage L3-N 

UINT32 

0,01 

0x0007 (7) 

voltage L1-L2 

UINT32 

0,01 

0x0009 (9) 

voltage L2-L3 

UINT32 

0,01 

0x000B (11) 

voltage L1-L3 

  UINT32 

             V 

              0,01 

0x000D (13) 

current L1 

UINT32 

0,01 

0x000F (15) 

current L2 

UINT32 

0,01 

0x0011 (17) 

current L3 

UINT32 

0,01 

0x0013 (19) 

current N 

UINT32 

0,01 

0x0015 (21) 

frequency L1 

UINT16 

Hz 

0,01 

0x0016 (22) 

frequency L2 

UINT16 

Hz 

0,01 

0x0017 (23) 

frequency L3 

UINT16 

Hz 

0,01 

0x0018 (24) 

active power L1 

INT32 

Watt 

0x001A (26) 

active power L2 

INT32 

       Watt 

             1 

0x001C (28) 

active power L3 

INT32 

Watt 

0x001E (30) 

active power total 

INT32 

Watt 

0x0020 (32) 

reactive power L1 

INT32 

var 

0x0022 (34) 

reactive power L2 

INT32 

var 

0x0024 (36) 

reactive power L3 

INT32 

var 

0x0026 (38) 

reactive power total 

INT32 

var 

0x0028 (40) 

apparent power L1 

INT32 

VA 

0x002A (42) 

apparent power L2 

INT32 

VA 

0x002C (44) 

apparent power L3 

INT32 

VA 

0x002E (46) 

apparent power total 

INT32 

VA 

0x0030 (48) 

power factor L1 

INT16 

 

0,01 

0x0031 (49) 

power factor L2 

INT16 

 

0,01 

0x0032 (50) 

power factor L3 

INT16 

 

0,01 

0x0033 (51) 

power factor total 

INT16 

 

0,01 

Содержание EZD-TCP

Страница 1: ...len Blindarbeit in kvarh oder Mvarh mit 5 2 Stellen Funktionsanzeigen LED f r Wirkarbeit Import und Export 10000 Impulse kWh Beide LED leuchten bei Strom Imin Reset Das Nullsetzen der Energiez hler ka...

Страница 2: ...h UL 94 V 0 Gewicht 220 g Abmessungen Anschluss EZD Achtung Die Ger te d rfen nur mit getrennten Stromwandlern betrieben werden Beim Anschluss der Eingangsgr e Strom ist die Stromrichtung zu beachten...

Страница 3: ...name in den Einstellungen ndern Die Werkseinstellung f r den Username ist admin und f r das Passwort 123ezd Weiterhin k nnen Sie sich auf einer Website die Messwerte anzeigen lassen Der EZG TCP und de...

Страница 4: ...eistung L1 3 VA kVA MVA Scheinleistung L2 8 Einheit Scheinleistung L2 3 VA kVA MVA Scheinleistung L3 8 Einheit Scheinleistung L3 3 VA kVA MVA Scheinleistung Summe 8 Einheit Scheinleistung Summe 3 VA k...

Страница 5: ...r Wirkenergie L3 Import 10 Einheit Wirkenergie L3 Import 3 kWh MWh Wirkenergie L3 Export 10 Einheit Wirkenergie L3 Export 3 kWh MWh Blindenergie L3 Induktiv 8 unit power factor L1 3 ind cap power fact...

Страница 6: ...istung L1 INT32 var 1 0x0022 34 Blindleistung L2 INT32 var 1 0x0024 36 Blindleistung L3 INT32 var 1 0x0026 38 Blindleistung Summe INT32 var 1 0x0028 40 Scheinleistung L1 INT32 VA 1 0x002A 42 Scheinlei...

Страница 7: ...0x0071 113 IP Adresse UINT32 X X X X 0x0073 115 Subnetmaske UINT32 X X X X 0x0075 117 Standardgateway UINT32 X X X X 0x0034 52 active energy T1 T2 import UINT32 kWh MWh Faktor Wirkarbeit Import 0x003...

Отзывы: