151058 – Delta P High Limit Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
151059 – FGP High Limit Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
151061 – Watchdog Reset
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
151064 – CAN Flow Demand Failed
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet setting is not correct.
u
Switch over setting to PWM input. Check PWM signal.
151066 – TecJet Shutdown
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet combined alarm. At least
one additional TecJet alarm is
pending.
u
Rectify the cause of the source alarm.
151067 – TecJet Internal Fault
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
151069 – Keyswitch State
Red alarm. Initiated by TecJet.
Cause
Corrective action
Keyswitch cabling missing.
u
Check cabling.
MS150059/01E 2012-07 | Troubleshooting | 77
TIM-ID: 0000017543 - 001