112719 – HIHI T-Exhaust B9 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Exhaust gas temperature of this
cylinder is too high.
1. Check emission values.
2. Check ignition timing (→ Page 154).
3. Check valve gear (exhaust valves do not close).
112720 – HIHI T-Exhaust B10 (abs)
Red alarm. Initiated by EMU.
Cause
Corrective action
Exhaust gas temperature of this
cylinder is too high.
1. Check emission values.
2. Check ignition timing (→ Page 154).
3. Check valve gear (exhaust valves do not close).
112923 – MD/SD T-Exhaust
Red alarm. Initiated by EMU.
Cause
Corrective action
Summary alarm (for details, refer
to the source alarm).
u
Summary alarm (for details, refer to the source alarm).
113200 – Communication Lost ECU
Red alarm. Initiated by SAM.
Cause
Corrective action
No communication with ECU CAN.
1. Check supply voltage.
2. Check connecting line.
113601 – AL Gas Valve 1 feedback
Red alarm. Initiated by SAM.
Cause
Corrective action
Feedback signal from valve 1 does
not correspond with setpoint
signal.
u
Check valve 1 and cabling.
113902 – SS Local Initiated Emerg. Stop
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop detected.
Emergency stop was released
manually (button), or ignition
system reported overspeed.
u
84 | Troubleshooting | MS150098/03E 2018-04
TIM-ID: 0000027854 - 002