506 – AL Low Starter Voltage
ZKP-Number: 14.500.906
Cause
Corrective action
battery voltage is too low to
accomplish a starting
procedure.
u
Check battery-charging generator and cabling.
507 – AL POM Error
ZKP-Number: 14.500.907
Cause
Corrective action
A general POM error occurred.
u
Replace POM.
508 – AL Wrong POM-ID
ZKP-Number: 14.500.908
Cause
Corrective action
POM transmits an unexpected
ID number. If alarm occurs in
combination with alarm 504, the
resistor in the POM cabling is
missing.
u
Check POM wiring harness.
519 – Oillevel Calibration Error
ZKP-Number: 10.158.921
Cause
Corrective action
Error when writing the
calibration value into the Flash
or SD memory of the level
sensor; associated PV: AL Group
6 Mot Bit 11
1. Check sensor and cabling, replace as necessary.
2. Contact Service.
525 – SD P-Lube Oil (R2)
ZKP-Number: 18.004.638
Cause
Corrective action
Redundant lube oil pressure
sensor faulty; Short circuit or
wire break
u
Check sensor and cabling, replace as necessary.
526 – SD T-Coolant (R2)
ZKP-Number: 18.004.639
Cause
Corrective action
Redundant coolant temperature
sensor faulty; Short circuit or
wire break
u
Check sensor and cabling, replace as necessary.
126 | Troubleshooting | MS150035/01E 2013-11
TIM-ID: 0000018389 - 003