7.7 Fuel System
7.7.1 Fuel system – Venting
Preconditions
☑ Engine is stopped and starting disabled.
Special tools, Material, Spare parts
Designation / Use
Part No.
Qty.
Diesel fuel
WARNING
Fuels are combustible.
Risk of fire and explosion!
• Avoid open flames, electrical sparks and ignition sources.
• Do not smoke.
Venting LP fuel system
1.
Open threaded vent plug (1).
2.
Unlock fuel priming pump (2), screw out
handle by turning it counterclockwise.
3.
Operate the pump with the handle (2) until
bubble-free fuel emerges at the threaded
vent plug (1).
4.
Close threaded vent plug (1).
5.
Screw in handle by turning it clockwise.
6.
Verify that fuel priming pump (2) is locked:
Handle must be tightened.
84 | Task Description | MS150054/02E 2012-02
TIM-ID: 0000004709 - 005