Specifications 

 
 

5. External Dimensions & Terminal Assignments

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6. Terminal Connection Diagram 

 

Terminal

No.

 

 

Note: For the single output model, the OUTPUT2 shown should be 

interpreted as N.C. 

 
 

7. Terminal Connection 

The following steps should be taken prior to the connection. 
 

 

 
 
 
 
 
 
 

8. Power Line Connection 

The terminals for power supply connection (

 and 

) are covered 

with a plastic plate for safety (see Fig. 1). 
Open the cover plate and connect the power lines to the terminals 
(see Fig. 2). 
Return the cover plate to its original position (see Fig. 3). 
 

4

5

1

2

P/+

N/-

4

5

4

5

Terminal Block
Cover

 

 
 
Note: For your safety, do not make any electrical connections or 

disconnections with power supplied to the instrument. Make 
sure that all terminal screws are properly tightened each time 
you finish the tightening. 

 

Input Resistance 

Voltage input: 

1M

Ω

 min. with or without power. 

Current input: 

4 to 20mA DC: 50

 (standard) 

2 to 10mA DC: 250

 

1 to 5mA DC: 100

 

0 to 20mA DC: 50

 

10 to 50mA DC: 10

 

Allowable Input 
Voltage 

Voltage input: 30V DC max., continuous. 
(Standard for a span up to 10V) 
Current input: 40mA DC max., continuous. 
(Standard for 4 to 20mA) 

Allowable Output 
Load 

Voltage output: 

1V span and up: 2mA max. 
10mV: 10k

 min. 

100mV: 100k

 min. 

Current output: 

Single current output: 

750

 max. (for 4-20mA output) 

Dual current output: 

Output 1: 550

 max. (for 4-20mA output) 

Output 2: 350

 max. (for 4-20mA output) 

Zero Adjustment 

Approx. ±5% of span. 
(Adjustable by the front-accessible trimmer.) 

Span Adjustment 

Approx. ±5% of span. 
(Adjustable by the front-accessible trimmer.) 

Accuracy Rating  Better than ±0.1% of span (at 25°C±5°C) 
Temperature 
Effect 

Better than ±0.2% of span per 10°C change in 
ambient. 

Response Time 

When Output 1 is voltage: 
80µs max. (0-90%) with a step input at 100%. 
(Frequency characteristics: 10kHz-3dB) 
When Output 1 is current: 
150µs max. (0-90%) with a step input at 100%. 
(Frequency characteristics: 3kHz-3dB) 

Insulation 
Resistance 

100M

Ω

 min. (@ 500V DC) between input, 

output 1, output 2, power, and ground. 

Dielectric 
Strength 

Input / [Output 1, Output 2] / [Power, Ground]: 
2000V AC for 1 minute (Cutoff current: 0.5mA) 
Power / Ground: 2000V AC for 1 minute (Cutoff 
current: 5mA) 
Output 1 / Output 2: 500V AC for 1 minute 
(Cutoff current: 0.5mA) 

Surge Withstand 
Capability 

Tested as per ANSI/IEEE C37.90.1-1989. 

Storage 
Temperature 

-10 to 60°C 

(1) Loosen the terminal screw. 

(2) Insert the tip of a 

screwdriver bit beneath 

the washer and push it 

up to make ample room 

to receive a cable.

 

Fig. 1 

Fig. 2 

Fig. 3 

1

2

4

5

6

7

8

9

10

11