MTT MS3739 Скачать руководство пользователя страница 4

  User's Manual 

MS3739 

Slim Plug-In Ratio/Bias Converter with Isolated Single/Dual Output 

 

Rev. 1.60 

9. Mounting / Demounting

 

Mounting the Socket on a DIN rail 

 

 

Demounting the Socket

 

 

 

 

Main Unit Installation / Removal 

 

Fixing Screw

I/O Pins

 

 
Installation 
(1)  Identify the top and the bottom of the unit and insert the I/O pins 

straight into the corresponding pin slots (receptacles) on the 
socket. 

(2)  Tighten the fixing screw to fix the unit firmly in position. 
 
Removal 
(1)  Loosen the fixing screw. 
(2)  Pull out the unit carefully not to bend the I/O pins. 
 

10. Ratio/Bias Setting 
10-1. Ratio Setting 

Set the Ratio/Bias Selector Switch to the “RATIO” position, and the 
Ratio/Bias Indicator will show the current ratio value. Press the UP 
or DOWN switch to change the value as desired. 

10-2. Bias Setting 

Set the Ratio/Bias Selector Switch to the “BIAS” position, and the 
Ratio/Bias Indicator will show the current bias value. Press the UP 
or DOWN switch to change the value as desired. 
Notes: 
- Unless otherwise requested, the ratio and bias will be set to the 

factory default settings indicated below: 
      Ratio = 1; Bias = 0% 

- The UP/DOWN switch is of a push button type. Pressing and 

holding the switch changes the value faster. 

- Setting ranges available are: 

Ratio: 0.1 to 4.00 for positive gain; -0.1 to -4.00 for negative gain 
(in 0.01 steps) 
Bias: -100 to 100% (in 1% steps)

 

 

 

 

11. LED Status Indicators

 

The MS3739 has LED status indicators to indicate its status. The 
following table shows indicator patterns. 

No. Event 

Ratio/Bias 

Indicator 

(7-segment 

LED) 

Polarity Indicator LED 

Output 

Recovery 
Operation 

Power ON or 
switch operation 

Blinks 3 times 
(1 s ON - 0.5 s 
OFF cycle). 

Green LED turns ON 
for 1 second, and then 
red LED turns ON for 
0.5 second. This cycle 
is repeated 3 times. 

Normal 

– 

Normal operation 

OFF 

Green LED is ON. 

Normal 

– 

Value setting 

Set value 

Red LED is ON when 
the set value is 
positive; Green LED is 
ON when it is negative. 

Normal 

– 

DAC error 

Error code: 1 

Red LED blinks at 0.25 
second intervals. 

Typically 
0%, but 
may vary. 

None 

CRC error of a 
set value 

Error code: 2 

Red LED blinks at 1 
second intervals. 

0% Reconfig-

uration 

CRC error of a 
compensated 
value 

Error code: 4 

Red LED blinks at 1 
second intervals. 

0% None 

System error 

Not defined. 

Red LED is ON; Green 
LED is not defined. 

Typically 
0%, but 
may vary. 

None 

Notes: 
#1: When the Ratio/Bias

 

Indicator is turned on, a 3-digit number “888” with dots is displayed. 

#4-7: Only the last digit is displayed in the event of an error. 
#7: The red LED may fail to light up. 

 

Hold the socket with the slide 
clamp facing down. Hook the upper 
edge of the cavity in the rear of the 
socket over the upper blade of the 
rail (

), then push the lower part of 

the socket against the lower blade 
of the rail so as to make the slide 
clamp engaged firmly with the rail 
(

). 

Push the slide clamp downward with 
a flat-head screwdriver bit or the like 
(

), and pull the lower part of the 

socket toward you (

).

 

Отзывы: