  User's Manual 

MS3705HB  Slim Plug-In Digital Alarm Setter with Isolated Dual Output (High Accuracy Model) 

 

Rev. 1.50 

10. Mounting / Demounting

 

Mounting the Socket on a DIN rail 

 

 

Demounting the Socket

 

 

 

 

Main Unit Installation / Removal 

 

Fixing Screw

I/O Pins

 

 
Installation 
(1)  Identify the top and the bottom of the unit and insert the I/O pins 

straight into the corresponding pin slots (receptacles) on the 
socket. 

(2)  Tighten the fixing screw to fix the unit firmly in position. 
 
Removal 
(1)  Loosen the fixing screw. 
(2)  Pull out the unit carefully not to bend the I/O pins. 
 
 

11. Settings

 

11-1 Trip Point Setting 

Setting for OUT-1: 
Set the OUT-1/2 Selector Switch to the RY1 position, and the Relay 
Trip Point Indicator will show the current trip point value for OUT-1. 
You can use the UP or DOWN Switch to change the value. 
Setting for OUT-2: 
Set the OUT-1/2 Selector Switch to the RY2 position, and the Relay 
Trip Point Indicator will show the current value for OUT-2. You can 
similarly change the value. 
Note: If no switch is operated for one minute, the indicators will 

automatically turn off. To turn the unlit indicators back on, 
press the UP or DOWN switch or move the OUT-1/2 Selector 
Switch to the opposite position. The Relay Trip Point Indicator 
and CPU Status Indicator will blink as shown in the table (#1) 
in section 12, and then the former indicator will show the 
current value. 

11-2 Mode Setting 

Turn on the power while holding down the DOWN Switch. After the 
CPU Status Indicator LED starts blinking, release the DOWN Switch. 
The Relay Trip Point Indicator will show the current relay activation 
mode for the output you have selected with the OUT-1/2 Selector 
Switch, i.e., OUT-1 when the it is in the RY1 position and OUT-2 
when in the RY2 position. You can use the UP or DOWN Switch to 
change the mode, referring to the table below. To make your 
change take effect, move the OUT-1/2 Selector Switch to the 
opposite position to where it is located. This enables the instrument 
to save the setting. After completing the setting, cycle the power to 
start operation in the mode you have selected. 

Mode Output 

Upper limit alarm; relay activated when alarmed. 

Upper limit alarm; relay deactivated when alarmed. 

Lower limit alarm; relay activated when alarmed. 

Lower limit alarm; relay deactivated when alarmed. 

11-3 Hysteresis Setting 

Turn on the power while holding down the UP Switch. After the CPU 
Status Indicator LED starts blinking, release the UP Switch. The 
Relay Trip Point Indicator will show the current hysteresis value for 
the output you have selected with the OUT-1/2 Selector Switch, i.e., 
OUT-1 when the it is in the RY1 position and OUT-2 when in the 
RY2 position. You can use the UP or DOWN Switch to change the 
hysteresis value. To make your change take effect, move the 
OUT-1/2 Selector Switch to the opposite position to where it is 
located. This enables the instrument to save the setting. After 
completing the setting, cycle the power to start operation based on 
the hysteresis you have set. 
 
Notes: 
1.  The UP/DOWN switch is of a push button type. Pressing and 

holding the switch changes the value faster. 

2.  Unless otherwise requested, the relay operation will be set to the 

factory default settings shown in the table below. 

Output Trip 

Point  Mode Hysteresis 

OUT-1 50% 

0  1.0% 

OUT-2 50% 

2  1.0% 

 

 

 

 
 

Hold the socket with the slide 
clamp facing down. Hook the upper 
edge of the cavity in the rear of the 
socket over the upper blade of the 
rail (

), then push the lower part of 

the socket against the lower blade 
of the rail so as to make the slide 
clamp engaged firmly with the rail 
(

). 

Push the slide clamp downward with 
a flat-head screwdriver bit or the like 
(

), and pull the lower part of the 

socket toward you (

).

 