11. Trip Point Setting
You can set trip points using the rotary switches on the front panel.
Refer to the table below and set the trip points by turning the rotary
switches with a screwdriver or the like.
Notes:
- The setting must be done with power off.
- Special care should be taken to avoid placing the rotary switch
halfway between dial indicator positions. Turn the switch until it
clicks into place and is firmly seated.
(Example)
When, with an input range of 0-5V, you want to set the trip points
for OUTPUT1 and OUTPUT2 to 4V and 2.25V, respectively, set
the rotary switches as follows:
Since 4V is 80% of the input span (5V), set the RY1-SET×10
switch to 8 and the RY1-SET×1 to 0.
Since 2.25V is 45% of the input span (5V), set the RY2-SET×10
switch to 4 and the RY2-SET×1 to 5.
Rotary Switch
Rotary Switch
Rotary Switch
Status Indicator
Status Indicator
Rotary Switch
12. Maintenance and Inspection
Check the unit for proper characteristics and settings about once
every two years.
13. Warranty Period and Scope
[Warranty Period]
MTT’s hardware products are warranted for a period of seven (7)
years from the date of shipment.
[Warranty Scope]
1) MTT warrants that its hardware products are free from defects
in materials and workmanship and conform to its product
specifications.
2) MTT ships the products under its appropriate quality
management system and quality control, but does not warrant,
expressed or implied, that the operation, output, or indication
of the hardware will be uninterrupted or error free. MTT shall
not be liable and make no warranty for any damage to or any
safety or performance trouble in the customer’s or any other
third party’s equipment if the operation, output, or indication is
interrupted or faulty.
3) If, during the warranty period, the product proves to be
defective when used in accordance with the relevant user’s
manual, the product will be repaired or replaced.
4) This warranty does not apply to any malfunction or failure
resulting from the following:
a. Improper or incomplete maintenance or calibration,
b. Any other cause, which does not relate with the delivered
product,
c. Modification or repair by any person other than MTT, and
d. Natural disasters or other unavoidable accidents, for which
MTT is not liable.
Output Switch
Dial
Indicator Position
OUTPUT1
RY1-SET×10
Number in the tens place of set
point (%) for input span
RY1-SET×1
Number in the ones place of set
point (%) for input span
OUTPUT2
RY2-SET×10
Number in the tens place of set
point (%) for input span
RY2-SET×1
Number in the ones place of set
point (%) for input span
8 0 %
└
Set RY1-SET×1 to 0.
Set RY1-SET×10 to 8.
4 5 %
└
Set RY2-SET×1 to 5.
Set RY2-SET×10 to 4.