7

 
 

Setting up Servo Loop Parameters

 

 

EDC User's Manual 

Chapter: 

3. Setup 

 

 

Section: 

Setting up Servo Loop Parameters 

 

       Servo Loop parameters include the proportional gain (Kp) and excess 

error (EX ERROR) of the Controller. It is important that you be able to set 
these parameters correctly for your application. Read the above section 
of the 

EDC User's Manual

 carefully before proceeding. 

       Power up the Controller. Press the Mode key until the top line of the 

display reads SETUP. Then press the 

t

 or 

s

 key until the second line 

of the display reads [X: LOOP] or [Y: LOOP]. Then press the F1 (EDIT) 
key to begin editing servo loop parameters for the X or Y axis. Follow the 
editing instructions in the 

EDC User's Manual

 to set the servo loop 

parameters as follows: 

• 

Set proportional gain (Kp) to 1.00 

• 

Set excess error (EX ERROR) to an acceptable value (this value 
depends on the scale value set earlier). 

• 

Set all other servo loop parameters to 0. 

 

     

 

Remove power from the Controller before proceeding. 
 

 
 
 

Encoder Test

 

 

EDC User's Manual 

Chapter: 

7. Monitoring 

 

       Perform this test only if you can power up and move the encoder without 

applying power to the servo drive or actuator. Take the following steps: 

• 

Power up the EDC Controller.  

• 

Press the MODE key until the top line of the display reads 
MONITOR.  Then press the 

t

 or 

s

 key until the top line of the 

display reads MONITOR  [POSN]. 

• 

Move the encoder by hand.  Encoder movement should cause a 
change in the position displayed on the Controller. (This test 
may cause an Excess Error fault. Ignore this fault at this time.) 

 

       If the Controller does not display the position, or if encoder movement is 

not accurately reflected on the display, repeat the procedure for setting 
Calibration Parameters. 

     

 

Remove power from the Controller before proceeding. 
 

 

Содержание MotionPlus EDC

Страница 1: ...MotionPlus EDC Encoder Digital Controller Getting Started Manual 2101 North Broadway 0901 New Ulm MN 56073 150604 00C Telephone 507 354 1616 MTS Systems Corporation 2000 Fax 507 354 1611...

Страница 2: ...ual Part No 150655 00 is essential You can t install or program the EDC without it If it s missing call the number below The Getting Started Manual Part No 150604 00 Problems If your EDC package is in...

Страница 3: ...arameters Servo command output connection Fault input connection Enable output connection Jogging the system and general check out A box is provided for each step By checking off each box you can be s...

Страница 4: ...splay screen and general operation of the EDC Controller Connecting AC Power EDC User s Manual Chapter 2 Installation Section AC Power Connections Procedure Follow the instructions in the above sectio...

Страница 5: ...Limits enables voltage other than 15 V Servo outputs if isolation is required or if maximum voltage between 10 V and 24 V is required Programmable I O if isolation is required if current greater than...

Страница 6: ...in the Setup Access menu Limit Inputs Turns off Enable output and zeroes Servo command when connection is open to ground Connect the Interlock Access and Limit inputs Test for accurate connection of...

Страница 7: ...bration Parameters EDC User s Manual Chapter 3 Setup Section Setting up Calibration Parameters Calibration parameters control the scale and movement of the actuator It is important that you be able to...

Страница 8: ...00 Set excess error EX ERROR to an acceptable value this value depends on the scale value set earlier Set all other servo loop parameters to 0 Remove power from the Controller before proceeding Encode...

Страница 9: ...ases component changes on the EDC If jumper or component changes are necessary remove power from the Controller before proceeding Then remove the Controller front cover as described in the EDC User s...

Страница 10: ...e with the EDC Controller enable output The EDC Controller enable is factory configured as ON low To set it for ON high jumper changes are necessary Before changing jumpers or making connections make...

Страница 11: ...2 Installation Servo Output Connections Swap the Command connection with the Command connection Press the Mode key until the top line of the display reads RUN MODE then follow the directions in the ab...

Отзывы: