Line  1:  Time  Delay  Emergency  to  Normal 
(TDEN) 

TDEN  delays  the  transfer  from  the  emergency  
back  to  the  grid,  permitting  the  stabilization  of  the 
grid  before  returning.  Timing  begins  when  the  grid 
becomes available.  

Adjustable TDEN time range: 0

0

 to 990 sec 

Line  2:  Time  Delay  Normal  to  Emergency 

(TDNE) 

TDNE delays the transfer from normal to emergency 
to  permit  stabilization  of  the  generator  before  the 

t

ransfer is made. Timing begins when the generator 

becomes available. 

(sometimes called the warm-up 

timer)

Adjustable TDEN time range: 0.0 to 250 sec 

Line 3: Time Delay Engine Start (TDES) 

This  timer  prevents  nuisance  start  because  of 
momentary  electrical  glitches.  If  power  normalizes 
before the countdown ends, the controller skips the 
engine start and resets the timer.   

Adjustable TDES time range: 0 to 30 sec 

Line  4:  Time  Delay  Engine  Cool-down 

(TDEC) 

TDEC  permits  the  generator  to  run  unloaded  after 
the ATS return to the grid. Timing begins when the 
ATS  connects  back  to  grid  power 

(If  you  already 

have  cool-down  on  the  Generator  Controler  this 

time is also added to the ATS cool-down timer)

Adjustable TDEC range: 0 to 999 sec 

Line 5: Time Delay Center OFF Position 

This timer temporally stops the switch in the center 
OFF position (completely cut off) before proceeding 
to normal. Useful is some computerizes system that 
need time in OFF to reset.     

Adjustable time delay range: 0 to 99 sec 

Lines  6,  7, 

8

,  & 

9

:  Over  /  Under  Voltage 

and Loss of one wire sensing 

The controller monitors the voltage from grid and 

the 

generator.

  The  client  can  program  over  &  under 

voltage window. (Refer to program table line 6, 7, 

8

& 9

 

O/V adjustment range : 110VAC to 300VAC 

O/V reset value: 

10VAC (Not adjustable) 

U/V adjustment range: 80VAC to 240VAC 

U/V reset value: +10VAC (Not adjustable) 

Programmable exerciser 

It can be set to exercise one time per week 

at 

any 

day and time, with load. The length of the exercise 
is  also  set.  (Refer    program

ming

    line

s

 

10

11

12

13

14

 & 

15

NOTICE 

COMMON ALARM

 provides 

AN

 auxiliary 

dry 

contact 

for  use  when  the  ATS  is  in

  

Emergency position

 (Its

 

ON only 

for 60 sec

)

ATS-22AGAG Automatic Transfer Switch 

______________________________________________________________________________________ 

2

REPLACEMENT PARTS

Replacement

 

parts

 

are

 

availabl

e

.

 

When

 

ordering

 

parts

 

provide

 

the Model and Serial Number. From

 

the

 

transfer

 

switch

 

name-Plate. Contact MTS Power

in United States call   1-800- 541-7677
World Wide call 305-634-1511

Содержание ATS-21AG

Страница 1: ...ATS 21 22AG Automatic Transfer Switch And Control PLC Operator s Manual MTS Power Products MIAMI FL 33142 Dedicated Single Phase Transfer Switch With Touch Screen Controls...

Страница 2: ...ion of customer connections Normal Power Connections Emergency Power Connections Manual Override LOAD Power Connections ATS 22AG Control and position indicators Remote Start plus Alarm connection Acti...

Страница 3: ...able for single phase systems only and including all necessary monitoring and protections The ATS 22AG features Smart touch screen touch sensor design Compact size with user friendly LED display All p...

Страница 4: ...range 0 to 999 sec Line 5 Time Delay Center OFF Position This timer temporally stops the switch in the center OFF position completely cut off before proceeding to normal Useful is some computerizes s...

Страница 5: ...by one unit If held the up button continues to scroll 2 3 2 Decrease Button When programming touching the down button decreases by one unit If held the down button continues to scroll 2 3 3 Auto Butto...

Страница 6: ...cy Normal grid over voltage Normal grid under voltage Normal grid over frequency Normal grid under frequency Emergency over voltage Emergency under voltage Emergency over frequency Emergency under fre...

Страница 7: ...rid power Permitting the controller to start the engine and carry out a power transfer UNDER load for 20 min After 20 Minutes the Control automatically return to AUTO If at anytime the Generator stops...

Страница 8: ...Under voltage protection setting 08 to 24 80V to 240V 18 180V 10 Set today s day of the week Day 1 to 7 Monday to Sunday current 11 Set today s hour Hour 00 to 23 current 12 Set today s minutes 00 to...

Страница 9: ...surement Range 40HZ to 75HZ Remote Start Contact 7A 250VAC Max Normal ON Contact 7A 250VAC Max Emergency ON Contact 7A 250VAC Max Auxiliary Contact Output 7A 250VAC Max Operating Temperature Storage T...

Страница 10: ...it Dimensions All Dimensions in MM 4 4 Installation Reference Silicon waterproof seal Panel Cut out A T S Metal door Fix bracket Screw Screw Fix bracket _______________________________________________...

Страница 11: ..._______________________________________________________________________________ 8 SECTION 5 TYPICAL WIRING AG Unit GENSET LOAD MAINS ATS 22AG Control Unit ELS Genset Auxiliary Switch NLS Normal Auxili...

Отзывы: