MTS Sensors Temposonics V RH5 Series Скачать руководство пользователя страница 30

Temposonics

® 

R-Series 

V

 SSI

Operation Manual

I 30 I

6.  Maintenance and troubleshooting

6.1 Error conditions, troubleshooting

See chapter “5. Commissioning” on page 23.

6.2 Maintenance

The sensor is maintenance-free. 

6.3 Repair

Repairs of the sensor may be performed only by MTS Sensors or  
a repair facility explicitly authorized by MTS Sensors. For return see 
chapter “2.6 Return” on page 4.

NOTICE

Changes to the sensor parameters must also be set to the control 
system.
Different parameter values on sensor and control systems can lead 
to unpredictable behavior of the control system.

Jitter Window:

 The jitter specifies the time interval between the

start of measuring and the SSI clock, which is given by the PLC
(for synchronous mode). Values between 0

255 μs can be set

for this parameter (default value: 50 μs). A larger value extends the
cycle time of the sensor.

Monoflop Time:

 Break between two consecutive bar sequences  

(Fig. 32). Values between 16

25 µs can be set for this parameter  

(default value: 16 µs).

Error Values:

 Setting the values which are transmitted in case of a

failure.

Power Failure:

 Setting the time from when a power failure is output.

Error Counter:

 Setting the number how often in the case of a failure

(1…255 times) the old measurement value will be repeated, before
the error value will be displayed.

After the settings have been configured, click the “EXIT COMMAND
MODE” button. A new menu for exiting the command mode will open.
Click the “SAVE AND EXIT” button to exit the command mode and
to transfer the changed settings to the sensor. The sensor returns
to the normal function and outputs the current position value. The
connection icon on the top right will turn to green. The status LED of 
the sensor flashes green.

6.4 List of spare parts

No spare parts are available for this sensor. 

6.5 Transport and storage

The conditions of transport and storage of the sensor match the oper-
ating conditions mentioned in this document.

7.  Removal from service/dismantling

The product contains electronic components and must be disposed  
of in accordance with the local regulations.

Содержание Temposonics V RH5 Series

Страница 1: ...GENERATION V THE NEW Temposonics R Series V SSI Operation Manual Temposonics Magnetostrictive Linear Position Sensors...

Страница 2: ...unit 18 4 7 Electrical connection 19 4 8 Frequently ordered accessories for sensor model RP5 20 4 9 Frequently ordered accessories for sensor model RH5 21 4 10 Frequently ordered accessories for SSI...

Страница 3: ...fined range Signal output is wrong no signal output the sensor will be damaged Position measurement is influenced by an external magnetic field Signal output is wrong Cables are damaged Short circuit...

Страница 4: ...dous areas The sensors are not suitable for operation in explosion hazardous areas 2 See also applicable MTS Sensors terms of sales and delivery on www mtssensors com 2 5 Warranty MTS Sensors grants a...

Страница 5: ...ly option 24 bit can be selected under l Data length j Options 0 Standard 1 Internal linearization a Sensor model R P 5 Profile b Design G Magnet slider backlash free part no 253 421 suitable for inte...

Страница 6: ...g direction forward synchronous mode 2 4 Measuring direction forward synchronous mode 3 5 Measuring direction reverse asynchronous mode 6 Measuring direction reverse synchronous mode 1 7 Measuring dir...

Страница 7: ...ronics housing NOTICE In this case only option 24 bit can be selected under l Data length j Options 0 Standard 1 Internal linearization 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 2...

Страница 8: ...S 0 0 2 FIR filter 2 measurements S 0 0 4 FIR filter 4 measurements S 0 0 8 FIR filter 8 measurements S 0 0 A No filter error counter 4 cycles S 0 0 C No filter error counter 8 cycles S 0 0 D No filte...

Страница 9: ...ing clamps up to 1250 mm 50 in stroke length 1 mounting clamp for each 500 mm 20 in additional stroke length RH5 rod sensor RH5 B Base unit without flange rod assembly 3 socket screws M4 RH5 J M S T S...

Страница 10: ...teraction of the magnetic fields releases a torsional strain pulse that propagates the length of the waveguide When the ultrasonic wave reaches the end of the wave guide it is converted into an electr...

Страница 11: ...nches Controlling design dimensions are in millimeters and measurements in are in inches Installation of RP5 The position sensor can be installed in any position Normally the sensor is firmly installe...

Страница 12: ...46 53 2 09 A F 44 5 1 75 51 3 2 02 RH5 T A V RH5 with threaded flange 16 UNF 3A with raised face example Connection type HXX PXX RXX TXX cable output A F 44 5 A F 1 75 51 3 2 02 25 4 1 Threaded flang...

Страница 13: ...nics housing 68 2 68 Null zone 51 2 01 Stroke length 25 5900 1 232 Threaded flange J M22 1 5 6g Magnet 12 7 0 13 0 5 0 01 Dead zone 73 6 2 9 11 7 0 46 RH5 B A V RH5 base unit only for replacement exam...

Страница 14: ...tion see chapter 4 6 Replacement of base unit on page 18 Fig 8 Mounting example of threaded flange Fig 9 Sensor in cylinder In the case of threaded flange M18 1 5 6g or M22 1 5 6g provide a screw hole...

Страница 15: ...be 15 mm 0 6 in Fig 15 If no other option exists and magnetic material is used observe the specified dimensions Fig 15 Magnet mounting with magnetic material When using magnetic material the dimensio...

Страница 16: ...eference edge of mounting Start position 48 5 1 91 End position 66 68 5 2 6 2 7 Stroke length 5000 mm 196 9 in RP5 with magnet slider S N V G Sensor electronics housing Reference edge of mounting Star...

Страница 17: ...g on the magnet points to the same direction as the screw in the lid of the sensor electronics housing which is located right of the status LED Fig 20 Alignment of ring magnet for RH5 SSI with interna...

Страница 18: ...24 for the sensor designs M S and T The sensor can be replaced without interrupting the hydraulic cir cuit 3 Insert the new base unit Install the ground lug on a screw Tighten the screws Fastening to...

Страница 19: ...and electronics earth connections no compensating currents are allowed to flow across the cable shielding Recommendation Install potential compensating leads with large cross section or use cables wi...

Страница 20: ...prox 25 g Operating temperature 40 85 C 40 185 F Position magnets Mounting accessories 32 8 1 29 23 8 0 94 13 5 0 53 4 3 0 17 60 140 3 0 12 7 9 0 31 19 5 0 77 1 5 0 06 33 1 3 14 0 55 20 5 0 81 14 9 0...

Страница 21: ...0 17 3 2 0 13 15 3 0 6 2 2 0 09 16 4 0 65 2 2 0 09 Block magnet L Part no 403 448 Magnet spacer Part no 400 633 O ring for threaded flange M18 1 5 6g Part no 401 133 O ring for threaded flange 16 UNF...

Страница 22: ...r friendly interface for mobile devices and desktop computers See data sheet TempoLink smart assistant document part no 552070 for further information Cables PVC cable Part no 530 032 PUR cable Part n...

Страница 23: ...0 Optocoupler 1 6 V 1 nF 1 nF Cable length 3 m 50 m 100 m 200 m 400 m Baud rate 1 MBd 400 kBd 300 kBd 200 kBd 100 kBd Clock T Standard one shot n T MSB Bit n Bit n 1 Bit 3 Clock Data High Low High Low...

Страница 24: ...ensor is out of the al lowable range Set the power supply for the sensor to the allowable range Extra magnet Sensor registers more position magnets than set Ensure that the number of position magnets...

Страница 25: ...connector of the adapter cable to the connection point labeled OUTPUT SENSOR on the TempoLink smart assistant Fig 35 NOTICE When disconnecting the power supply of the sensor possibly error messages oc...

Страница 26: ...ing to the connector wiring in Fig 41 Fig 42 There are two ways to connect the TempoLink smart assistant to a power supply 1 Connection via the plug in power supply with plug adapters Attach the plug...

Страница 27: ...cable with the micro USB connector to the port labeled USB on the TempoLink smart assistant Fig 44 2 Next connect the USB type A connector to a free USB port of the computer The USB connection simulat...

Страница 28: ...cludes information about the operational settings of the connected sensor Fig 48 To change parameters or to reset the sensor to factory settings the command mode must be started In command mode the se...

Страница 29: ...the internal linearization Enabled NOTICE Enabled can only be activated if the sensor was ordered with the option internal linearization Disabled Filter Configuration Setting of the filter for the out...

Страница 30: ...16 25 s can be set for this parameter default value 16 s Error Values Setting the values which are transmitted in case of a failure Power Failure Setting the time from when a power failure is output E...

Страница 31: ...imum 25 m 30 m 50 m 90 m 150 m 190 m Repeatability 0 001 F S minimum 2 5 m typical Hysteresis 4 m typical Temperature coefficient 15 ppm K typical Operating conditions Operating temperature 40 85 C 40...

Страница 32: ...nection Connection type 1 M16 male connector 7 pin or cable output Operating voltage 12 30 VDC 20 9 6 36 VDC Power consumption 1 2 W typical Dielectric strength 500 VDC DC ground to machine ground Pol...

Страница 33: ...Operating temperature 40 85 C 40 185 F Humidity 90 relative humidity no condensation Ingress protection IP67 connectors correctly fitted IP68 for cable output Shock test 150 g 11 ms IEC standard 60068...

Страница 34: ...nection Connection type 1 M16 male connector 7 pin or cable output Operating voltage 12 30 VDC 20 9 6 36 VDC Power consumption 1 2 W typical Dielectric strength 500 VDC DC ground to machine ground Pol...

Страница 35: ...e or several sensors for checking or repair we need you to sign a safety declaration The purpose of this declaration is to ensure that the returned items do not contain residues of harmful substances...

Страница 36: ...See Detail C 3 4 16 UNF 2B Thread See Notes 3 And 4 32 in 32 in 125 in B 1 105 in Minimum Full Thread Depth 0 875 in dia 0 015 0 000 0 769 in dia 0 015 0 000 0 500 in dia 0 005 in dia FIM A 45 5 15 1...

Страница 37: ...ecreasing from sensor electronics housing to rod end profile end P Parity The parity bit is a check bit that is added to a bit string to detect transmission errors There are even parity and odd parity...

Страница 38: ...m JAPAN Zweigstelle Telefon 81 3 6416 1063 E Mail info jp mtssensors com www mtssensors com MTS Temposonics und Level Plus sind eingetragene Warenzeichen der MTS Systems Corporation in den USA MTS Sen...

Отзывы: