18
INM9312-FB-ST-SS-1
Oct 2008
18
APPENDIX 1 - TECHNICAL DATA
Explosion protection
Fieldbus Barrier
II 2 (1) G D Ex mb e ib [ia] IIC/IIB T4
module
BVS 06 ATEX E 135X
Ta = –40°C to +75°C
Spurs “FISCO“ according to IEC 60079-27
suitable enclosure neccessary
Fieldbus Barrier
II 2 (1) G EEx mb ed ib [ia] IIC T4
enclosure:
PTB 01 ATEX 1001
Ta = –40°C to +70°C
Spurs “FISCO“ according to IEC 60079-27
Installation
in Zones 1 and 2, Zones 21 and 22 (dust), with suitable enclosure
Safety data (CENELEC)
each spur
FISCO (IEC 60079-27)
Max. voltage Uo
15.7V
Max. current Io
245mA
Max. power Po
960mW
Max. connectable capacitance
Co for IIC / IIB
476nF / 2878nF
Max. connectable inductance
Co for IIC / IIB
0.58mH / 2.9mH
Max. internal capacitance Ci 1.1nF
Max. internal inductance Li ~ 0mH
Insulation voltage Um
253V
Power supply
powered from the trunk
Galvanic isolation
(to EN 50020)
Ex i spurs to Ex e trunk
1.5kV (test voltage)
Ex i spur to Ex i spur
no isolation
Data transmission
between trunk and spurs
passive, no repeater function
Trunk,
non intrinsically safe / Ex e
Connections
2 trunk connections (in, out), internally interconnected
Voltage range
16 – 32V
Low voltage monitoring
U < 16V, spurs de-energized
Max. DC current
at 16 V
at 24V
at 32V
0 mA each spur
32mA
26mA
23mA
20 mA each spur
223mA
147mA
112mA
7 spurs @ 20 mA,
1 spur in short-circuit 265mA
172mA
132mA
short-circuit all spurs < 90mA
< 70mA
< 60mA
Max. power dissipation
1.8W
Indication
LED green “PWR“
(U
≥
16V on trunk)