TECHNICAL MANUAL
Chapter 9
- User - Control Interface
NGSi 05÷15
16
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited
9 . 2
P a r a m e t e r s c a t e g o r y
9 . 3
S e t p o i n t s s e t t a b l e b y t h e u s e r
The second setpoint is only operational if the relative optional kit has been purchased.
9 . 4
D i s p l a y
Normally, the display shows the water output temperature in tenths of a degree Celsius or the alarm code if at least one alarm has been
tripped. With several alarms present, the first one is shown and the second one appears after the first has been reset. In menu mode, the
contents of the screen depend on the function being used.
9 . 5
L E D s
Description
Group identification
code
Parameter index
Configuration
CnF
H01-
Compressor
CP
C01-
Fan
FAn
F01-
Alarms
ALL
A01-
Adjustment
Re
b01-
Pump
PUP
P01-
Electric heaters
Fro
r01-
Defrosting
dFr
d01-
Electronic valve
EEu
U01-
Offset
OFF
o01-
Setpoint type
Setpoint
(summer/winter)
Summer
default (range)
Winter
default (range)
First setpoint [°C]
Coo/Hea
7 (5÷18)
45 (35÷55)
Second setpoint [°C]
Co2/He2
18 (7÷23)
35 (25÷45)
Hot water setpoint [°C]
San
48 (25÷55)
Compressor LED
•
ON with compressor in operation.
•
OFF with compressor not running.
•
FLASHING if compressor start delay timer is running.
Domestic hot
water LED
•
ON with domestic hot water valve active.
•
OFF with domestic hot water valve not active.
Defrost LED
•
ON with defrosting active.
•
OFF with defrosting disabled or completed.
•
FLASHING if defrosting interval timer is running.
Antifreeze heater
LED
•
LED ON with antifreeze heater (optional) in operation.
Pump LED
•
LED ON with pump in operation.
Alarm LED
•
LED ON with an alarm tripped.
Heating mode
LED
•
LED ON with unit in heating mode.
Cooling mode
LED
•
LED ON with unit in cooling mode.
Содержание NGSi 05