background image

 

 

ATA 61-07-60 

 
 

7.3 

ADVANCED/NEW INSTALL OPERATION WITH I/O FEATURES (J1 WIRED, J2 WIRED) 

 
This mode makes use of additional features like external heater-enable, Self-test activation or weight-on-
wheels deactivation. An overview of this features follows in table 8. 
 
For this mode power of J1 has to be supplied. After power supply the EDC will perform a Self-test to check 
the correct function of the De-Icing and the EDC for up to 7 seconds. After that the heating sequence can 
be started by “Heater-Enable” 
 

Function 

Description 

Heater-Enable 

Activates heater outputs if Heater-Enable is activated (pulled to ground). 

Self-Test 

Triggers the device Self-test if activated (connected to ground). The 
usage is optional. 

WoW 

Deactivates heater outputs if WoW signal active (connected to ground). 
The usage is optional. 

Warning Output 
(normally closed) 

Indicates device failures,failure of Deice-System (Deice Boots, Wires, 
etc…) and status as described in 7.3.5. Normally closed (connected to 
ground) switch is active if EDC is unsupplied. Can be used to detect loss 
of supply power. The usage is optional. 

Warning Output 
(normally open) 

Indicates device failures, failure of Deice-System (Deice Boots, Wires, 
etc…) and status as described. Normally open (not connected to ground)  
switch is open if EDC is unpowered. The usage is optional. 

Table 8: Special Functions 

 

7.3.1 

Functional checks referring to 1.3.1 

 
The Self-test described under 7.3.3 covers all needed checks. It could be performed anytime the De-Icing 
is not operating. 
If the Warning Output is inactive after a Self-test, the EDC is in an airworthy condition. 
 

7.3.2 

Heater-Enable 

 
To use this input, the EDC must be supplied permanently with supply voltage. The heating sequence will 
then be activated by the heater-enable signal. After disable the heating sequence will be reset. 
 
 

7.3.3 

Self-Test 

 
The  advanced  EDC  includes  a  Self-test  function  which  checks  functionality  of  internal  control  logic, 
warning output and output loads. 
 
The Self-test is executed at every power up (power supply J1-P). During Self-test, the warning output is 
active  for  3-7  sec.,  allowing  a  lamp  test  of  the  connected  warning  lamps.  After  the  Self-test  was  run 
successful, the EDC is ready for normal operation, indicated by an inactive warning output. If the Self-test 
was not successful, the warning output remain active. 
 
The Self-test procedure can be triggered any time if the device has power supply but output sequence is 
not active. The Self-test input can be connected to a push button or switch. Be aware when using a switch 
that the device remains in Self-test mode if the switch state is active. 
 

Important: 
The Self-test with propeller inoperating could fail sometime and the warning will be active due to 
not sufficient electrical contact of the brush blocks. 
Repeat  the  Self-test  with  engine  running,  the  warning  will  be  reset  if  the  current  is  inside  the 
operational range. 

 

 

Page 14 

 

Original Issue   

2021-07-01 

Содержание E-3760

Страница 1: ...8 EASA 21J 020 E 3760 ATA 61 07 60 OPERATION and INSTALLATION MANUAL ELECTRIC DE ICE CONTROLLER Original Issue July 1st 2021 The technical content of this document is approved under authority of DOA N...

Страница 2: ...tial that the MT Electric De Ice Controller be properly maintained according to the recommended service procedures and a close watch be exercised to detect impending problems before they become seriou...

Страница 3: ...2 Table of valid pages 3 MT Propeller Airworthiness Information 4 1 General 5 2 Applicable and referenced documents 5 3 System Overview 7 4 Technical Specifications 8 5 System Interconnections 9 6 Ins...

Страница 4: ...ATA 61 07 60 LIST OF REVISIONS No Date of Revision Page Short Description Original Issue 2021 07 01 All Pages Initial Issue Page 2 Original Issue 2021 07 01...

Страница 5: ...Page Date of revision 0 1 2021 07 01 1 2021 07 01 2 2021 07 01 3 2021 07 01 4 2021 07 01 5 2021 07 01 6 2021 07 01 7 2021 07 01 8 2021 07 01 9 2021 07 01 10 2021 07 01 11 2021 07 01 12 2021 07 01 13...

Страница 6: ...m time to time issues Service Bulletins Service Letters and Manuals relating to the propeller and its installation Service Bulletins are of special importance and should be complied with promptly Thes...

Страница 7: ...schedule is available 150 flight hours For turboprop application if no time schedule is available 1 3 2 Overhaul Period No additional overhaul time limitations 1 3 3 Airworthiness Limitation Section N...

Страница 8: ...ND Ground IMA Installation Manual MDL Master Documents List MT MT Propeller Entwicklung GmbH P N Part Number OAT Outside Air Temperature RF Radio Frequency RTCA Radio Technical Commission for Aeronaut...

Страница 9: ...fine the time and order in which the outputs are enabled For control via external systems advanced EDC models accepts discrete input signals e g heater enable self test or weight on wheels To provide...

Страница 10: ...ment Connector J1 provides input for supply power and system ground Furthermore up to four power supply output channels are provided by J1 depends on actual device configuration see Table 3 J2 exists...

Страница 11: ...on Not applicable Environmental Qualification DO 160G Altitude Up to 50 000 ft Operating Temperature 40 C to 70 C Table 5 Qualifications Overview Refer to chapter 9 for further qualification informati...

Страница 12: ...4 Reserved for future use Reserved for future use 5 Heater enable Open GND GND Input 6 Self test Open GND GND Open Input 7 Reserved for future use Reserved for future use 8 Warning Open GND normally...

Страница 13: ...e 35 Reserved for future use Reserved for future use 36 Reserved for future use Reserved for future use 37 Reserved for future use Reserved for future use Table 7 Pin Assignment of J2 Notes Leave unus...

Страница 14: ...wire connector J2 It is connected to the internal eletronic and damage is possible if connected 6 2 NEW INSTALLATION ADVANCED SETUP J1 AND J2 have to be connected and used 6 2 1 Installation Consider...

Страница 15: ...in chapter 5 2 7 OPERATION 7 1 GENERAL OPERATION INFORMATION As the EDC is designed for use as retrofit replacement but also for new installations there are two main operation modes depending on mode...

Страница 16: ...ferring to 1 3 1 The Self test described under 7 3 3 covers all needed checks It could be performed anytime the De Icing is not operating If the Warning Output is inactive after a Self test the EDC is...

Страница 17: ...ring failure Thresholds depending on P N see table 3 Heating not disabled Additionally the normally closed warning output can be used to indicate loss of supply power 7 3 6 Logical Behavior Inputs Ou...

Страница 18: ...ATA 61 07 60 Figure 3 Installation Drawing 8 DRAWINGS Page 16 Original Issue 2021 07 01...

Страница 19: ...tion S Test curves T 10 g PK 9 7 Explosive atmosphere X N A not tested 10 3 1 Waterproofness X N A not tested 11 4 1 Fluids susceptibility X N A not tested 12 4 Sand and dust X N A not tested 13 0 Fun...

Отзывы: