5.6
Commissioning of expansion modules EP- 05
Up to five expansion modules (EP- 05) with five alarm relays each can be connected via the RS- 485 bus. Each
connected EP- 05 expansion module is registered in the menu “System parameters”. To recognize the position of
the EP- 05 modules a module address is assigned to each module via the address switch.
The table shows the assignment of the relay numbers to the module addresses.
Module- Addr. Relay No.
Analog
Outout No.
1
06 to 10
03 to 04
2
11 to 15
05 to 06
3
16 to 20
07 to 08
4
21 to 25
09 to 10
5
26 to 30
11 to 12
With the DGC- 05 systems by MSR-E, the complete configuration of the EP- 05 modules is already factory-set.
Configuration only is necessary with single modules or in case of retrofitting or exchange of a module.
The address switch is located behind the connecting plug X1. Unplug X1 for addressing.
5.7
Fitting of system parameters
At commissioning the alarm relays must be assigned to the alarms (thresholds) for each measuring point. For all
other parameters the values are deposited as defaults, which can be changed at any time if necessary.
See also „Description of PolyGard Gas Controller DGC- 05”.