Ultima MOS-5 Detector
4.4.1 Ultima
MOS-5
Intelligent Sensor User Menu Structure
Operate
“- -”
“SE”
Time Out
Reset
Relays
Enter Gas Check Mode
Enter Calibration
Mode
“Sr”
Set Sensor Range
20,50,100 ppm
“Fi”
“AC”
“rSt”
Gas
Detected?
Gas
Removed?
Reset Sensor Life
to 100%
Apply Gas and
Remove When
Complete
N
Y
N
Reset Sensor
Life?
“Co”
“Lo”
Warm Relay
“Hi”
Alarm Relay
“CH1”
Modbus Ch. 1
“Fi”
Finished
“CH2”
Modbus Ch. 2
Setpoint
Latching or
Non-Latching
Energized or
De-Energized
“Fi”
Energized or
De-Energized
Latching or
Non-Latching
Setpoint
“Fi”
Enable
Disable
“Fi”
Baud
Rate
Address
Data
Format
“Fi”
Baud
Rate
Data
Format
Address
“Fi”
“Hrt”
Enable
Disable
“Fi”
If Hart installed
Y
N
If Hart Enabled
N
Y
Hm – Hold magnet
Am – Apply magnet
Rm – Remove magnet
N – No
Y - Yes
Hm
Hm
Hm
Hm
Fault
Y
Rm
Rm
Rm
Rm
Am
Am
Am
Am
Am
Am
Am
Am
Am
“SE”
Hm
Rm
N
If Hart Enabled
Y
N
Figure 12: User Menu Structure
NOTE:
“Co” stands for Calibration Output. When “Co” is enabled and calibration is
successful, the analog output goes from 1.5 mA to 3.2 mA for five seconds, settling
at the desired value of 4 mA. This option is commonly used with the MSA Model
10000 Controller system.
4.4.2 Sensor
Range
The sensor range is selectable between 0-20 ppm, 0-50 ppm, or 0-100 ppm depending on the
installed sensor. To adjust the sensor range of the Ultima MOS-5 Intelligent Sensor, apply the
magnet to the MSA logo on the cover of the unit until “
SE
” is displayed, then remove the
magnet. This puts the unit into setup mode. After a few seconds “
Sr
” will be displayed. Apply
and remove the magnet to adjust the sensor range. The current sensor range will be displayed.
To change the sensor range, apply and remove the magnet repeatedly until the desired range
is displayed. Once the desired range is displayed, wait three seconds and “
Fi
” will be displayed.