![MSA PS-303 Series Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/msa/ps-303-series/ps-303-series_operating-manual_1846523013.webp)
Operating Manual
12
d)
transfer a piano type switch on the Product’s casing to “ON” position;
e)
take off the cover and measure output voltage of connector Х8 (terminals
1, 2
and 3, 4) by voltmeter, see Figure 2. Voltage shall be 24 V or 12 V DC depending on
the Product type. If the voltage does not comply with the abovementioned, the Product
is not considered to be ready for operation; contact the Manufacturer;
f)
if the Х8 voltage complies with the abovementioned, transfer piano type
switch and a circuit breaker of switchboard to «OFF» position. Connect load to Х8
connector;
g)
close the cover and transfer a circuit breaker of switchboard and piano type
switch on the Product casing to “ON” position; check the load operation.
2.2.4
To switch The Product off:
a)
Switch the load off (only if it may be switched off by a breaker on its casing,
otherwise, the load switches off after the Product’s powering off);
b)
Transfer a piano type switch on the Product’s casing to “OFF” position then
transfer circuit breakers of main power switchboard to «OFF» position».
2.3
U
SAGE OF THE PRODUCT
To use the Product:
a)
Switch on a circuit breakers of main power switchboard;
b)
Transfer a piano type switch on the Product’s casing to “ON” position.
Availability of main or standby power is indicated by LED glowing: «Main» or
«Standby» respectively, see Figure 1.