MSA fieldserver QuickServer FS-QS-2 0 Series Скачать руководство пользователя страница 10

Installation 

 
 
 

 

 QuickServer Start-up Guide 

10 

 
 

3.2

 

Connecting the R1 & R2 Ports 

For the R1 Port only: 

Switch between RS-485 and RS-232 by moving the number 4 DIP Switch left for 

RS-485 and right for RS-232 (

Figure 5

). 

The R2 Port is RS-485. 

Connect to the 3-pin connector(s) as shown below. 

 

3.2.1  Wiring 

RS-485 

RS-232 

BMS RS-485 

Wiring 

Gateway Pin   

Assignment 

BMS RS-232 

Wiring 

Gateway Pin   

Assignment 

RS-485 + 

TX + 

RS-232 - 

TX + 

RS-485 - 

RX - 

RS-232 + 

RX - 

GND 

GND 

GND 

GND 

NOTE:  Use standard grounding principles for GND. 

3.2.2  Supported RS-485 Baud Rates by Protocol  

The supported baud rates for either port is based on the protocol of the connected devices. 

The following baud rates are supported for Modbus RTU: 
2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 

The following baud rates are supported for BACnet MS/TP: 
9600, 19200, 38400, 76800 

 

Figure 5: R1 & R2 Connection Ports 

TX+ RX- GND

+

-

GND

Содержание fieldserver QuickServer FS-QS-2 0 Series

Страница 1: ...QuickServer Start up Guide 0 Start up Guide QuickServer FS QS 2XX0 MSAsafety com Document Revision 2 B T18627 APPLICABILITY EFFECTIVITY Effective for all systems manufactured after March 2021...

Страница 2: ...Safety 1991 Tarob Court Milpitas CA 95035 Website www MSAsafety com U S Support Information 1 408 964 4443 1 800 727 4377 Email smc support msasafety com EMEA Support Information 31 33 808 0590 Email...

Страница 3: ...fault Untrusted Self Signed TLS Certificate or HTTP with Built in Payload Encryption 17 7 Configuring the QuickServer 18 7 1 Configure Network Settings 19 7 1 1 Using FS GUI to Input Network Settings...

Страница 4: ...nge Security Mode 45 10 2 2 Edit the Certificate Loaded onto the FieldServer 46 10 3 Change User Management Settings 47 10 3 1 Create Users 48 10 3 2 Edit Users 49 10 3 3 Delete Users 50 10 3 4 Change...

Страница 5: ...onnections Screen 25 Figure 25 Generic Web App Page First Login 26 Figure 26 SMC Cloud Opt Out Warning Window 27 Figure 27 Welcome to SMC Cloud Email 28 Figure 28 Setting User Details 29 Figure 29 SMC...

Страница 6: ...ements the BACnet features claimed in the listing The mark is a symbol of a high quality BACnet product Go to www BACnetInternational net for more information about the BACnet Testing Laboratory Click...

Страница 7: ...de 7 2 Equipment Setup 2 1 Mounting The QuickServer can be mounted using the DIN rail mounting bracket on the back of the unit NOTE For dimension details see Section 10 7 Figure 1 DIN Rail Bracket Fig...

Страница 8: ...the logic The bias resistor is 510 ohms which is in line with the BACnet spec It should only be enabled at one point on the bus for example on the field port were there are very weak bias resistors of...

Страница 9: ...ure 4 Termination resistor is also used to reduce noise It pulls the two lines of an idle bus together However the resistor would override the effect of any bias resistors if connected NOTE The R1 and...

Страница 10: ...eway Pin Assignment BMS RS 232 Wiring Gateway Pin Assignment RS 485 TX RS 232 TX RS 485 RX RS 232 RX GND GND GND GND NOTE Use standard grounding principles for GND 3 2 2 Supported RS 485 Baud Rates by...

Страница 11: ...configuring the QuickServer via the Web App To connect the QuickServer either connect the PC to the Router s Ethernet port or connect the Router and PC to an Ethernet switch Use Cat 5 cables for the...

Страница 12: ...hould be added to the power supply of the host system A safety margin of 25 is recommended Figure 7 Required Current Draw for the Gateway Apply power to the QuickServer as shown below in Figure 8 Ensu...

Страница 13: ...Control Panel click Network and Internet and then click Network and Sharing Center Click Change adapter settings on the left side of the window Right click on Local Area Connection and select Properti...

Страница 14: ...r as untrusted This will cause the following pop up windows to appear When the Web Server Security Unconfigured window appears read the text and choose whether to move forward with HTTPS or HTTP When...

Страница 15: ...the Username default is admin and the Password found on the label of the FieldServer NOTE There is also a QR code in the top right corner of the FieldServer label that shows the default unique passwor...

Страница 16: ...reen will appear that allows the user to select which mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Sec...

Страница 17: ...rase fields will appear under the mode selection Copy and paste the Certificate and Private Key text into their respective fields If the Private Key is encrypted type in the associated Passphrase Clic...

Страница 18: ...oud button see Figure 16 allows users to connect to the SMC Cloud MSA Safety s device cloud solution for IIoT The SMC Cloud enables secure remote connection to field devices through a FieldServer and...

Страница 19: ...GUI page to the Network Settings page follow the below instructions Find the Navigation tree across the left side of the screen Click the orange arrow next to the ProtoNode CN number and title to exp...

Страница 20: ...for the FieldServer s internet and network connections Click the Add Rule button to add a new row and set a new Destination Network Netmask and Gateway IP Address as needed Set the Priority for each c...

Страница 21: ...ult Gateway and Domain Name Server1 2 NOTE If the FieldServer is connected to a router the IP Gateway of the FieldServer should be set to the same IP Address of the router Click Save to record and act...

Страница 22: ...ice registers in the Config csv file for the initial start up If not the product is shipped with a sample config csv that shows an example of the drivers ordered In the main menu of the FS GUI screen...

Страница 23: ...Setup then File Transfer and finally Update Browse and select the csv file open then click Submit Once download is complete a message bar will appear confirming that the configuration was updated succ...

Страница 24: ...he main menu of the FS GUI screen click Setup then File Transfer Click the config csv link under the Retrieve heading in the middle section of the screen o The file will automatically download to the...

Страница 25: ...ver supplements and configuration manual MSA Safety also offers a technical support on the MSA Safety website which contains a significant number of resources and documentation that may be of assistan...

Страница 26: ...rver and hosts local applications for device configuration management as well as maintenance For more information about the SMC Cloud refer to the SMC Cloud Start up Guide 8 1 Choose Whether to Integr...

Страница 27: ...lick on a tab other than the SMC Cloud tab then click the checkbox next to Opt out of SMC Cloud Registration in the Warning window that appears and click the Exit Registration button o To ignore SMC C...

Страница 28: ...C Cloud from the manufacturer s support team and follow the instructions below to set up login details The Welcome to SMC Cloud email will appear as shown below NOTE If no SMC Cloud email was received...

Страница 29: ...ber password fields and click the checkbox to agree to the privacy policy and terms of service NOTE If access to data logs using RESTful API is needed do not include in the password Click Save to save...

Страница 30: ...ickServer can be registered onto the SMC Cloud server When first logging onto the QuickServer the Web App will open on the SMC Cloud page NOTE If a warning message appears instead go to Section 10 9 t...

Страница 31: ...gateway details and SMC Cloud account credentials o Enter user details and click Next o Enter the site details by entering the physical address fields or the latitude and longitude then click Next Fi...

Страница 32: ...ption required then click Next o Click the Create an SMC Cloud account button and enter a valid email to send a Welcome to SMC Cloud invite to the email address entered Figure 32 SMC Cloud Registratio...

Страница 33: ...will appear Click the Close button and the following screen will appear listing the device details and additional information auto populated by the QuickServer NOTE Update these details at any time b...

Страница 34: ...tion as per registration credentials NOTE If the login password is lost see the SMC Cloud Start up Guide for recovery instructions On first login the Privacy Policy window will appear Read the Terms o...

Страница 35: ...SMC Cloud Setup QuickServer Start up Guide 35 NOTE For additional SMC Cloud instructions see the SMC Cloud Start up Guide Figure 37 SMC Cloud Landing Page...

Страница 36: ...s Device Manager List and that it is configured to run the TCP IP protocol Check that the IP netmask of the PC matches the QuickServer The Default IP Address of the QuickServer is 192 168 2 X Subnet...

Страница 37: ...UI page and click on Diagnostics in the Navigation panel o Open the FieldServer Toolbox software and click the diagnose icon of the desired device Go to Full Diagnostic and select the capture period C...

Страница 38: ...s the power light and should always be steady green when the unit is powered RX The RX LED will flash when a message is received on the serial port on the 3 pin connector If the serial port is not use...

Страница 39: ...Next Gen Recovery 9 5 Internet Browser Software Support The following web browsers are supported Chrome Rev 57 and higher Firefox Rev 35 and higher Microsoft Edge Rev 41 and higher Safari Rev 3 and h...

Страница 40: ...ation Add TLS_Port parameter in the connections section of the configuration file and set to a port number between 1 65535 Connections Adapter Protocol TLS_Port N1 Modbus TCP 1502 This configuration s...

Страница 41: ...ldServer with the following connection settings Connections Adapter Protocol TLS_Port Validate_Client_Cert Cert_Authority_File N1 Modbus TCP 1502 Yes my_authorized_clients pem This configuration has t...

Страница 42: ...synonymously known as common name host name or domain etc The common name can be obtained by the following methods Ask the certificate issuer for the host name Use online tools to decode the certific...

Страница 43: ...s certificate against its own internal authority file before finalizing the connection By default this means the FieldServer will only establish connections to other FieldServers Remote_Node_TLS_Port...

Страница 44: ...r Initial Setup NOTE Any changes will require a FieldServer reboot to take effect Navigate from the QuickServer landing page to the FS GUI by clicking the blue Diagnostics text on the bottom of the sc...

Страница 45: ...uide 45 10 2 1 Change Security Mode Click Security in the Navigation panel Click the Mode desired o If HTTPS with own trusted TLS certificate is selected follow instructions in Section 6 2 1 Click the...

Страница 46: ...e will only be available if the security mode was previously setup as HTTPS with own trusted TLS certificate Click Security in the Navigation panel Click the Edit Certificate button to open the certif...

Страница 47: ...rd on the label For recovery instructions see the FieldServer Next Gen Recovery document If the default unique password is lost then the unit must be mailed back to the factory NOTE Any changes will r...

Страница 48: ...oup and Password o User details are hashed and salted NOTE The password must meet the minimum complexity requirements An algorithm automatically checks the password entered and notes the level of stre...

Страница 49: ...s Click the pencil icon next to the desired user to open the User Edit window Once the User Edit window opens change the User Security Group and Password as needed Click Confirm Once the Success messa...

Страница 50: ...n QuickServer Start up Guide 50 10 3 3 Delete Users Click the trash can icon next to the desired user to delete the entry When the warning message appears click Confirm Figure 47 Setup Users Figure 48...

Страница 51: ...quirements An algorithm automatically checks the password entered and notes the level of strength on the top right of the Password text field NOTE If a gateway in the field is updated to a secure gate...

Страница 52: ...erver Part Numbers Field Connections Interface Connections RS 2321 RS 4852 RS 4223 KNX6 RS 485 M Bus Ethernet4 LonWorks5 QuickServer FS QS 2X10 1 2 1 FS QS 2X20 1 2 1 FS QS 1011 1 1 1 FS QS 1211 1 1 1...

Страница 53: ...perating temperature range o Meet the current and voltage rating for QuickServer Net Furthermore the interconnecting power cable shall o Be of length not exceeding 3 05m 118 3 o Be constructed of mate...

Страница 54: ...15 of the FCC Rules Operation is subject to the following two conditions This device may not cause harmful interference This device must accept any interference received including interference that ma...

Страница 55: ...o to the network settings by clicking the Settings tab and then click the Network tab o Check with the site s IT support that the DNS settings are setup correctly o Ensure that the ProtoAir is properl...

Страница 56: ...ich original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage...

Отзывы: