background image

Description 

 
 
 

 

Gardner Denver Driver Manual 

 
 

Description 

The Gardner Denver Auto Sentry ES/RS2000 driver allows the FieldServer to transfer data from devices 
over either RS-232 or RS-485 using Gardner Denver Auto Sentry ES/RS2000 protocol.  The driver can be 
configured  to  communicate  with  ES  Controllers  with  software  versions  V2.0X,  V2.1X  and  RS2000 
Controllers with software versions V4.0X  

The client driver implements the following functionality: 

 

Polls controllers for service and maintenance data. 

 

Polls controllers for operating mode data. 

 

Polls controllers for operating data. 

The driver can poll up to 8 units connected to one ES/RS2000 Controller. It always sets the active unit on 
the ES/RS2000 Controller before polling for data even if consecutive polls are for the same unit. This is 
done to prevent synchronization problems. 

Gardner Denver ES/RS2000 Controllers implements three message types for which the driver can poll. The 
driver  does  not  validate  the  message  data  fields  for  correct  values  although  it  does  validate  data  field 
lengths, for example, shutdown codes reported by V2.1 ES Controllers range from 0 to 27. If a code of 28 
is reported, the driver will not flag it as an error since codes have to be interpreted by the operator. However, 
a message length longer than 2 digits will be reported as an error. 

FieldServer Mode 

Nodes  Comments 

Client 

A  client  node  can  communicate  with  up  to  8  units  connected  to  a 
ES/RS2000 Controller 

Driver Scope of Supply 

2.1

 

Supplied by MSA Safety 

Part # 

Description 

FS-8917-16  UTP cable (7 foot) for RS-232 use 
FS-8917-03  RJ45 to DB9M connector adapter 

 

2.2

 

Provided by the Supplier of 3

r d

 Party Equipment 

2.2.1  Required 3

r d

 Party Hardware 

Part #  Description 

ES/RS2000 controller 

2.2.2  Required 3

r d

 Party Configuration 

The  ES/RS2000  Controller  must  be  set  up  in  the  correct  mode  to  support  either  RS-232  or  RS-485 
communications to an external monitoring system. Please refer to manufacturer’s setup instructions. 

2.2.3  Optional Items 

Part # 

Vendor/Manufacturer  Description 

485LDRC  B&B Electronics 

RS-232/RS-485 converter 

Содержание fieldserver FS-8700-60

Страница 1: ...er Denver Driver Manual 0 Driver Manual FS 8700 60 Gardner Denver MSAsafety com Driver Revision 1 03 Document Revision 3 A APPLICABILITY EFFECTIVITY Effective for all systems manufactured after March...

Страница 2: ...A Safety 1991 Tarob Court Milpitas CA 95035 Website www MSAsafety com U S Support Information 1 408 964 4443 1 800 727 4377 Email smc support msasafety com EMEA Support Information 31 33 808 0590 Emai...

Страница 3: ...ameters 8 5 2 Client Side Node Descriptors 8 5 3 Client Side Map Descriptor Parameters 9 5 3 1 FieldServer Specific Map Descriptor Parameters 9 5 3 2 Driver Related Map Descriptor Parameters 9 5 3 3 T...

Страница 4: ...e driver does not validate the message data fields for correct values although it does validate data field lengths for example shutdown codes reported by V2 1 ES Controllers range from 0 to 27 If a co...

Страница 5: ...ons The FieldServer is connected to the ES RS2000 Controller as shown in the connection drawing below Configure the ES RS2000 Controller according to manufacturer s instructions RS 485 Connection Gard...

Страница 6: ...e White Rx Tx GND Brown Connect to the RS 232 port on the FieldServer FS 8917 03 Pinouts FS Function DB9F Pin TX 2 RX 3 GND 5 CTS 8 3 1 Hardware Connection Tips Hints If inter controller communication...

Страница 7: ...Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Format Provide data format Each Data Array can only take on one format Float Bit Byte Uint...

Страница 8: ...Baud Specify baud rate 1200 9600 match to Controller Parity Specify parity Odd Even None Data_Bits Specify data bits 7 8 Stop_Bits Specify stop bits 1 2 Poll_Delay Time between internal polls 0 2s 0 2...

Страница 9: ...alues Node_Name Name of Node to fetch data from One of the node names specified in Client Node Descriptor above Gar_Cmd Data poll commands Service_Data Operating_Mode Operating_Data Gar_Data Data fiel...

Страница 10: ...ple Function Active Read Block Continuous Map Descriptor function responsible for polling the Controller Gar_Cmd The Gar_Cmd field is used to select the data to poll Gar_Data The Gar_data field is set...

Страница 11: ...matching Node_Name and Gar_Cmd fields It then stores the data items as specified by the Gar_data field from the data collected by the preceding active Map Descriptor 6 2 Poll Data Length The length o...

Страница 12: ...lect Unit Polls for Single Units Connected The device must be in Sequence Mode not Standalone mode The unit can be put in sequence mode setting the Units in Sequence to a number greater than 1 If usin...

Страница 13: ...aintenance B Hours 37 Oilage Unknown see ES RS2000 controller spec Operating Mode Data 0 Operating mode indication see ES RS2000 Controller spec 1 Sequence number2 see ES RS2000 Controller spec 2 Unit...

Отзывы: