OPERATION
MSA
14
Chillgard
M-100
GB
4.3. RS-485 Output Specifications
Register Name
PDU Address LOGICAL
Address Range
Fault and Module State
0x0000
1
Under Range
2 (msb)
Under Voltage
8 (msb)
Temperature
10
(msb)
Lamp
Fail
40
(msb)
Test Mode
80 (msb)
Warm Up Complete
0 (lsb)
Cal/Setup
2
(lsb)
Factory Mode
4 (lsb)
Trouble Mode
8 (lsb)
Gas Number
0x0001
2
0 to 40 (see below)
Gas Concentration
0x0002
3
-20 to 1050 (ppm)
Temperature
0x002C
45
-300 to +650 (°C * 10)
Humidity
0x002D
46
0 to 100 (%RH)
Gas Numbers
R-22 = 6,
R-123 = 12
R-404a = 27
R-134a = 15
Baud rate: 19,200; each byte is eight bits with no parity and two stop bits.