7.6.10Error Messages
LED Display
(Ver 3.05 and earlier)
LED Display
(Ver 3.07 & later)
Description
NO SENSR
NO SENSR
Unable to detect sensor assembly
Err: 0x02
DIG INP!
Digital Input status
Err: 0x20
SNS RNGE
Sensor ADC readings out of range
Err: 0x40
SNS FAIL
Too many 1-wire communication errors
Err: 0x80
NO SENSR
Faulty 1-wire initialization - too few devices
Err: 100
SNS TYPE
Sensor Initialization Error (no Type)
Err: 200
SNS TBL
Forced Trouble (Test Condition)
Err: 400
SNS LOW
Very low sensor output - down indicator
Err: 800
SNS LOW
Very low sensor output (<5% for Oxygen sensor)
COM SNSR
SNS FAIL
Internal sensor communication error
SMC 5100-XX-IT Toxic Gas Detector Module
39
US