Issue 1.1

Figure 2

 

Typical Wiring Diagram

Product Wiring

1.  IMPORTANT

: ensure all electrical connections are isolated before commencing any work on 

the unit.

2.  Power to the thermostat is provided via the Live and Neutral input terminals labelled “L” and 

“N” (85 - 265V AC, 50 - 60Hz).

3.  NOTE

:  This thermostat MUST be earthed using the earth terminal provided.

4.  Two voltage-free relay outputs capable of switching loads of up to 10A, 250V AC (resistive) are 

provided by the thermostat for controlling a fan convector.

5.  The “FAN” terminal is connected to the “HI” terminal when the thermostat has selected the High 

fan speed, conversely, it is connected to the “LO” terminal when the Low fan speed is selected.

6.  The “COM” terminal is connected to the “TX” terminal when the fan is to be On, conversely it is 

disconnected when the fan is to be Off.

7.  The “Remote Switch” input selects the ‘High’ Set-Back mode when it is closed and the ‘Low’ 

Set-Back mode when it is open.

8.  The temperature sensor is factory fi tted to all models with the exception of the Remote Sensor 

(/RS) versions.  A 2-core screened cable connection should be made to the “Temp. Sensor” 
terminals on /RS versions, with the screen connected to the thermostat Earth terminal only.

9.  CAUTION:

  The remote switch and temperature sensor inputs are not electrically isolated from 

the thermostat mains supply and so could possibly be at mains potential.  Treat the inputs with 
the necessary safety and insulation precautions as if they were at mains potential.

Installation 

1.  IMPORTANT

: ensure all electrical connections are isolated before commencing any work on 

the unit.

2.  Unscrew the 4 security screws using M.S. Electronics tamperproof screwdriver MSD-152 to 

remove the front cover.

3.  Mount the unit securely using any suitable fi xing in conjunction with the mounting holes 

provided in the unit.  For optimal results, position the temperature sensor out of direct sunlight 
and well away from any heating/cooling sources.

4.  Using Figures 2 to 5 as a guide, connect the wiring in a suitably appropriate form with the 

convenient pluggable terminal blocks provided.  Contact Technical Support with the heater 
make and model number for specifi c help if a suitable wiring method is unclear.

5.  On the remote sensor version, 2-core screened cable should be used to connect the remote 

sensor to the thermostat.  The screen should be connected to the earth terminal ONLY (do not 
connect the screen to anything at the remote sensor end).

6.  Adjust the internal controls to suit the operational requirements (see the ‘Operation’ section).
7.  Replace the cover securely using the 4 security screws.

Figure 2

Typica