MRW Vib-Control 04
16 v. 34
27. Oktober 2014
Structure
and function
Menu display
Activ.
button
Display
Navig.
button
Description
Save
button
Speed input
Internal/Buttons
External 0-10V =
xx V
External
potentiometer=
xx%
Whether the speed is to be controlled via
the control unit or via external inputs is
set here. The status of the external inputs
is displayed.
Start/Stop
Internal/Buttons
+24V Stop = xxV
+24V Start = xxV
Whether the vibratory drive is to be
activated by the buttons or via an
external input can be set here.
The input can be inverted.
The applied voltage at the input is
displayed.
MAX sensor
+24V Stop = xV
0V Stop = xV
The vibratory drive can be stopped here
via a MAX sensor.
The input can be inverted.
The applied voltage at the input is
indicated in the display.
MIN sensor
+24V Start = xV
0V Start = xV
The vibratory drive can be started here
via a MIN sensor.
The input can be inverted.
The applied voltage at the input is
indicated in the display.
Gentle start
Gentle start x.xs
0.5s
The delay for the gentle start can be set
here for between 0.1 and 9.9 seconds.
During this time, power is slowly
increased up to a preset target value.
Gentle stop
Gentle stop x.xs
0.5s
The delay for the gentle stop can be set
here for between 0.1 and 9.9 seconds.
During this time, power is slowly reduced
to a stop.
Stop delay
Time xx.s
0.5s
How long the signal on the MAX sensor
must be at “high level” before the
vibratory drive is stopped is set here.
Start delay
Time xx.s
0.5s
Without MIN sensor: How long the signal
on the MAX sensor must be at “low level”
before the vibratory drive is stopped is
set here.
With MIN sensor: how long the signal on
the MAX sensor and on the MIN sensor
must be at “low level” before the vibratory
drive is stopped.
Max speed xx%
Max speed xx%
90%
The maximum permissible speed of the
vibratory drive in % is set here.
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL