Alternative Port Capabilities
42
MRV Communications, Inc.
www.mrv.com
451-0331
Figure 13 - Typical Alarm Inputs Connections
An external voltage within the range of ±10V is required in order for a change to be detected when the
contact opens or closes. Typically, an LX-Series Control Output is used to provide the controlling
voltage for the Alarm Inputs, but it is not required. An external voltage could be used as long as it is
within both the ±10V limits and the limits of the contacts or semiconductor used in the circuit. A
common Signal Ground is required. Refer to Figure 13 for typical implementations.
Important design issues to remember are:
•
Electro-mechanical contacts must be rated up to 10V and 3.5mA.
•
The inputs present a nominal 5K Ohm impedance but can vary from 3K to 7K Ohm.
•
Input levels must be 0.6V or lower to guarantee a low state and 2.4V or higher to guarantee a
high state.
•
LX-Series products do not support the use of TXD as the controlling voltage for Alarm Inputs.
DTR or RTS must be used.
•
DTR or RTS can provide the controlling voltage for up to 2 Alarm Inputs each.
•
A common Signal Ground is required. Twisted pair connections are recommended to reduce
sensitivity to noise.
Note that provisions for handling alarm contact bounce and alarm flooding are available in the IR-
7104 Alarm Manager family only.
Control Output Setup and Usage
The LX-Series can be configured to provide two low voltage/low current Control Outputs per port
using the DTR and RTS output signals. Typically the Control Output is used as the controlling
voltage for the LX-Series Alarm Inputs. In another case you can design an interface to transition
from the output signals to a higher capacity circuit to implement a control subsystem. An example
circuit is shown in Figure 14.
Important design issues to remember are:
•
Special design attention is required when using Control Outputs in a control subsystem.
Содержание LX-8000 Series
Страница 4: ...4 MRV Communications Inc www mrv com 451 0331 ...
Страница 8: ...8 MRV Communications Inc www mrv com 451 0331 ...
Страница 10: ...10 MRV Communications Inc www mrv com 451 0331 ...
Страница 24: ...Installing the LX 8000 Series 24 MRV Communications Inc www mrv com 451 0331 ...
Страница 44: ...Alternative Port Capabilities 44 MRV Communications Inc www mrv com 451 0331 ...
Страница 48: ...Appendix A Technical Specifications 48 MRV Communications Inc www mrv com 451 0331 ...