Figure 1. Clearance Requirements

Do Locate the Unit:

With  proper  clearances  on  sides  and  top  of  unit  (a 

minimum of 12” on the three sides, service side should 

be 24” and 48” on top

On solid, level foundation or pad

To minimize refrigerant line lengths

Do Not Locate the Unit:

On brick, concrete blocks or unstable surfaces

Near clothes dryer exhaust vents

Near sleeping area or near windows

Under eaves where water, snow or ice can fall directly 

on the unit

With clearance less than 2 ft. from a second uni

With clearance less than 4 ft. on top of unit

Indoor Coil Piston Selection

The outdoor section must be matched to a factory approved 

indoor section. It is mandatory that the installer ensure that 

the correct piston or TXV is installed in the indoor section. 

If necessary remove the existing piston and replace it with 

the  correct  piston  or  TXV.  See  indoor  unit  instructions 

for  details  of  changing  the  piston  or  TXV.  Contact  your 

distributor for accessory piston kits.

The  correct  piston  size  is  shipped  with  the  outdoor  unit, 

piston that comes with the indoor unit, unless it matches 

the one listed on the outdoor unit.

Refrigeration Line Sets

Use only refrigeration grade copper tubes. Split systems 

may be installed with up to 50 feet of line set (no more than 

20 feet vertical) without special consideration. For lines 50 

feet or longer, refer to long line set guidelines.

Do  not  leave  the  lines  open  to  the  atmosphere  for  any 

period of time, moisture, dirt and bugs may contaminate 

the lines.

Filter Drier

and  reliability.  If  the  drier  is  shipped  loose,  it  must  be 

void, if the drier is not installed.

Model

13/16 SEER

Liquid Line

Suction Line

18

3/8

3/4

24

3/8

3/4

30

3/8

3/4

36

3/8

7/8

42

3/8

7/8

48

3/8

7/8

60

3/8

1-1/8

* Fittings should be supplied by the installer.

Table 1. 

Installation of Line Sets

DO NOT

 fasten liquid or suction lines in direct contact with 

type  of  hanger.  Keep  both  lines  separate,  and  always 

insulate the suction line. Long liquid line runs (30 feet or 

more) in an attic will require insulation. Route refrigeration 

line sets to minimize length.

DO NOT

 let refrigerant lines come in direct contact with 

foundation.  When  running  refrigerant  lines  through  the 

foundation  or  wall,  openings  should  allow  for  a  sound 

and vibration absorbing material to be placed or installed 

between  tubing  and  foundation.  Any  gap  between 

with a vibration damping material.

Содержание Signature MAC16 A Series

Страница 1: ...anual carefully before installation and keep it for future reference The Signature Series is NOT designed for amateur installation Installation SHOULD be performed by an authorized technician Please r...

Страница 2: ...e performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING result in hazards to you and others Installation MUST conform with local building codes and wi...

Страница 3: ...th RTV or other silicon based caulk 6 Avoid direct tubing contact with water pipes duct work 7 Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct...

Страница 4: ...nless it matches the one listed on the outdoor unit Refrigeration Line Sets Use only refrigeration grade copper tubes Split systems may be installed with up to 50 feet of line set no more than 20 feet...

Страница 5: ...utdoor unit 3 Follow the vacuum pump manufacturer s instructions Allow the pump to operate until the system has been evacuated down to 300 microns Allow the pump to continue running for an additional...

Страница 6: ...e to suction valve service port Determine saturation temp from T P chart 3 Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service val...

Страница 7: ...service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic t...

Страница 8: ...507043 04C Page 7 of 9 mrcool com Figure 3 A C Single Phase Wiring Diagram single speed condenser fan...

Страница 9: ...Page 8 of 9 507043 04C mrcool com Figure 4 A C Single Phase Wiring Diagram multi speed condenser fan...

Страница 10: ...rom the condenser coils SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY W...

Страница 11: ...or manual are subject to change without prior notice Consult with the sales agency or manufacturer for details ELECTRICIAN and or HVAC TECHNICIAN LICENSE INSTALLATION DATE INSTALLATION LOCATION SERIAL...

Отзывы: