4.2.2 Start/Stop Temperature Control Mode
Start/Stop mode control the temperature by setting two temperatures (target
control temperature
T_00
and control precision
T_01
). When the water
temperature of the reservoir is higher than
T_00+T_01
, compressor starts to
cooling , and it stops until the temperature lower than
T_00-T_01
. If set
T_00
=20
℃
and
T_01
=5
℃
, then the unit will control the temperature between
15
℃
and 25
℃
; when the water temperature is higher than 25
℃
, the compressor
starts to cooling, and the Auxiliary display shows the target cooling temperature
as 15
℃
; when the water temperature is lower than 15
℃
, the compressor stops to
cooling, at the same time the Auxiliary display shows the temperature up per limit
as 25
℃
.