3 Product description
Maschinenfabrik Reinhausen GmbH 2015
33
4349315/00 EN
VACUTAP® VR®
The pressure-operated relay works on the same principle as a barometric
corrugated tube with a counter-pressure spring and a mechanically linked
snap-action switch. The sensor on the snap-action switch snaps to the other
position by itself after tripping and has to be reset into the initial position by
hand.
The pressure increase activates the sensor on the snap-action switch that
flips into the OFF position. This triggers the circuit breaker and de-energizes
the transformer.
Low-energy interference does not cause the pressure-operated relay to trip
since the required tripping pressure is not reached. The tripping pressure is
set at the factory and prevented from being changed.
The pressure-operated relay responds faster than the RS 2001 protective re-
lay in relation to large pressure increases. The RS 2001 protective relay is
part of the default MR protection system that comes standard.
Additional use of a pressure-operated relay also requires installation of the
provided RS 2001 protective relay.
The features and characteristics of the pressure-operated relay comply with
the respective applicable version of IEC publication 60214-1.
Diverter switch operations at the rated switching capacity or permitted over-
load do not cause the pressure-operated relay to trip.
The pressure-operated relay responds to a pressure change and not to gas
accumulation under the pressure-operated relay. Gas accumulation under
the pressure-operated relay is normal.
Performance features
The product is particularly characterized by the following properties:
▪
High temperature range
▪
Large electrical switching capacity range of the main switching contacts
▪
High insulation strength
▪
High dielectric strength to ground
Structure/versions of the pressure-operated relay
This chapter gives you an overview of the structure of the pressure-operated
relay.
3.5.2
3.5.3
Содержание VACUTAP VR
Страница 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Страница 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Страница 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Страница 266: ......
Страница 267: ......