14 Appendix
Maschinenfabrik Reinhausen GmbH 2015
231
4349315/00 EN
VACUTAP® VR®
Appendix
Limit values for dielectric strength and water content of on-
load tap-changer oil
The following table provides the limit values for dielectric strength (measured
in accordance with IEC 60156) and water content (measured in accordance
with IEC 60814) of the on-load tap-changer oil for VACUTAP® on-load tap-
changers. The values have been established on the basis of IEC 60422.
U
d
H
2
O
When commissioning the transform-
er for the first time
> 60 kV/2.5 mm
< 12 ppm
During operation
> 30 kV/2.5 mm
< 30 ppm
After maintenance
> 50 kV/2.5 mm
< 15 ppm
Table 15: Limit values for on-load tap-changer oil